ABB 1SDA067908R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA067908R1
Manufacturer
ABB
Part number
1SDA067908R1

Quick Summary

The Moulded Case Circuit Breaker ABB 1SDA067908R1 provides reliable overcurrent protection for low-voltage distribution panels. Design teams often struggle to select devices that meet evolving OEM requirements, safety standards, and wiring constraints. This model aligns with IEC 60947-2 and delivers CE conformity, with UL and VDE certifications not required for this variant. With a 4P fixed-front-terminal configuration and a 10 A rating, it simplifies panel wiring and reduces maintenance downtime—driving total cost of ownership down. In addition, ABB EcoSolutions framing and recyclable and environmental data support sustainability goals across modern control architectures.

Product Information

Extended Description

1SDA067908R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
c8fca649-2ed8-4eb2-a7f1-f368452944a0 China (CN)
Simplified SCIP
3487f43c-dc99-4412-8966-643f48ec5522 Spain (ES) | 0f178fe3-81b1-42cb-9ad9-c4d7d5729b66 Germany (DE) | 6a34f033-fd18-4ab0-b535-71b3f4c02095 Sweden (SE) | 31b865bb-c6bf-4b86-90b5-e0cb141afeb3 Germany (DE) | 678733d0-90fc-49dd-920f-05ae0225a15f Belgium (BE) | 65904998-8b4d-4f1e-b30e-86da558b0be5 France (FR) | aab6c95b-d3ea-425e-8fc1-15ba2ac34f9a Bulgaria (BG) | f869bad2-c0bd-40e8-aed6-7da99a0a59c4 Sweden (SE) | 18316f78-52e2-4ad1-b646-bbc06868c315 Greece (GR) | 71b9016d-b0e1-4b53-9165-29bbbbea799e Portugal (PT) | 03c9df32-dc57-4af6-a280-d8bcff781982 Hungary (HU) | cfa5cc52-34a4-468b-92a2-7525f7eeb875 Poland (PL) | d64b596f-8793-4da0-a98d-5409f9584081 Netherlands (NL) | 75255fa1-7aaf-4a81-bab7-c0f20a0f8635 Estonia (EE) | 24424a3e-d4f8-42ac-bb83-c7575aec5469 Poland (PL) | 0ba8a362-29f4-4d23-bf9b-938e3f2a7183 France (FR) | 47b2c132-e0f9-4b75-a634-3fe5e5ce093d Czech Republic (CZ) | c7eb9e8e-fc37-47aa-adae-0d4847be1c73 Germany (DE) | dfd382b3-f500-47e0-a9b4-0302902939ee Denmark (DK) | 574e14df-db38-4ad2-97ec-bf6e14dd4543 Belgium (BE) | 7a291177-f934-4dfd-8e89-7d1709dc4922 Norway (NO) | 0f72ed97-6606-477f-8ca7-c28523e6e385 Germany (DE) | 22c95209-4f6b-4ae2-8282-a6ce3d9fb9c3 Finland (FI) | e900f4eb-bc41-4b05-8ffc-37a6f94076ee Germany (DE) | 19ff0d9b-5895-4151-bd9b-de7677b0085e Croatia (HR) | b7f742e2-a150-4abb-8bf6-9186a224b184 Poland (PL) | cc375343-b152-4e9d-b038-5da7abd7e0a1 Hungary (HU)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4010GFF000XXX
EAN
8015644018047
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644018047
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P fixed-front-terminal XT2 design enables rapid wiring and secure busbar connections, reducing installation time in control panels and minimizing field wiring errors for motor control and power distribution. This translates to lower commissioning costs and faster time-to-prod for packaged equipment. Feature → Business Impact → Application: Ekip LSIG solid-state release delivers precise tripping characteristics and stable protection against short circuits, improving selectivity and minimizing nuisance trips in dynamic load profiles such as HVAC suites and transformer feeders. Feature → Business Impact → Application: Rated current of 10 A and a 690 V operating voltage support compact protection in small to mid-size LV switches, enabling reliable transformer and panel protection without over-sizing components. Feature → Business Impact → Application: Front terminal connections, bolt-type terminals, and a 6 N·m tightening torque streamline maintenance and service routines in rugged industrial environments, reducing downtime during inspections and replacements. Feature → Business Impact → Application: IEC 60947-2 compliance, RoHS/REACH declarations, and documented EPDs provide regulatory assurance and support for sustainability reporting in energy-management projects. Feature → Business Impact → Application: 1.6 kg weight and 0.10 W per pole power loss contribute to lighter assemblies and incremental energy efficiency gains in large panel racks and SCADA-driven substations.

Get a Quick Quote for a ABB 1SDA067908R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA067908R1? Enquire Now

FAQs

Ensure front-terminal connections are accessible for wiring and maintenance. Use a main circuit screwdriver (M6 suggested) and tighten to the specified 6 N·m. Wire with busbar options in the 32.5 to 100 mm² range and confirm compatible panel spacing to avoid overcrowding. The 120 mm width and 130 mm height fit standard enclosures, while the 4P configuration supports multi-circuit protection in compact spaces.
The Ekip LSIG solid-state release provides precise tripping characteristics, improving selectivity and reducing nuisance trips in dynamic loads. Its fast opening time (30 ms in specified modes) enhances protection for motors and transformers, while maintaining reliable performance under varying fault conditions. The release is designed to integrate cleanly with front-terminal wiring for straightforward maintenance.
Yes. With a rated voltage of 690 V AC and a high short-circuit breaking capacity at common LV voltages, it protects transformer feeders effectively. Its 4P design supports multi-pole protection schemes, and IEC 60947-2 compliance ensures compatibility with standard LV switchgear. For extreme fault levels, verify applicable Ics/Icu values at your operating voltages to determine suitability.
The device carries CE conformity (EC Declaration of Conformity) and IEC 60947-2 compliance. Environmental data include an EPD for Tmax XT2 and ECO-solutions information, with RoHS and REACH declarations. Recyclability is specified at 55.70% per EN45555. CMRT and SCIP identifiers are provided for supply-chain sustainability reporting as part of ABB’s eco-friendly approach.
ROI comes from faster installations and reduced downtime thanks to front-terminal wiring, a robust 4P configuration, and a reliable LSIG release. With a power loss of 0.10 W per pole and a weight of 1.6 kg, overall energy and handling efficiency improve in large panel builds. A 1 piece minimum order and standardized dimensions further simplify procurement and stocking, supporting scalable deployments.