ABB 1SDA067910R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA067910R1
Quick Summary
ABB 1SDA067910R1 is a 4‑pole moulded case circuit breaker designed for reliable protection in industrial switchgear. Installation and maintenance are simplified with front terminals and a solid‑state LSIG release, reducing commissioning time and nuisance trips. This device carries CE certification via the EC Declaration of Conformity, alongside GL and Lloyd’s Register certificates, confirming compliance with IEC60947-2 and European safety expectations. Built for modern low‑voltage power distribution, it supports scalable protection in automation panels while delivering cost‑effective reliability for critical machinery and processes.
Product Information
Extended Description
1SDA067910R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 63 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
f791d40e-525f-4bc6-8bea-b9946b78731c China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4063GFF000XXX
EAN
8015644018061
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644018061
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.70 W
Rated Current (In)
63 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front terminals and fixed 4P XT2H design streamline installation and wiring, delivering faster commissioning and fewer field connections. Business Impact: Reduced on-site labor, lower risk of wiring errors, and quicker fault isolation in live panels. Application: Ideal for switchgear assemblies and distribution boards in industrial automation where compact, dependable protection is essential. Feature: Ekip LSIG solid‑state release provides precise, reliable tripping with documented response times. Business Impact: Improved selectivity and reduced risk of collateral outages, translating to higher line uptime and safer maintenance windows. Application: Motor feeders and transformer protection in automated systems that demand deterministic protection. Feature: Rated current 63 A and rated operational voltage 690 V AC enable compatibility with standard European low‑voltage power rails. Business Impact: Enables single‑source protection for multiple loads, lowering spare parts and stocking requirements. Application: Power distribution panels serving CNC machines, conveyors, and packaging lines. Feature: IEC60947‑2 compliance with CE DoC plus GL and LR certifications reinforces regulatory readiness. Business Impact: Streamlined approvals for European installations and multinational projects, reducing procurement risk. Application: Capital equipment and turnkey builds where formal certifications drive procurement confidence. Feature: Durability and lifecycle specs—electrical 8000 cycles per hour, mechanical 25,000 cycles—support frequent switching with predictable wear patterns. Business Impact: Lower maintenance frequency, reduced downtime, and extended service life in high‑cycle environments. Application: Automated line protection where frequent contact and fault clearance are expected.
Get a Quick Quote for a ABB 1SDA067910R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067910R1?
Enquire Now
FAQs
This 4P XT2H breaker uses front terminal connections and accepts busbars from 32.5 to 100 mm². Tightening torque is 6 N·m, and the unit supports a 690 V AC system. Plan for a compact panel layout and ensure clear access to the front terminals during maintenance.
Key specs include a rated current of 63 A, rated operational voltage of 690 V AC, and a short‑circuit rating aligned with IEC60947‑2. The LSIG release provides reliable tripping, with opening times around 30 ms under typical fault conditions, and it supports four poles for comprehensive protection.
Yes. It carries a CE Declaration of Conformity for Tmax XT2 family products and has GL and Lloyd’s Register certificates, reflecting robust third‑party validation. IEC60947‑2 is the governing standard, ensuring compatibility with European electrical installations.
The LSIG solid‑state release and 4P configuration provide precise protection with fast response, while front terminals simplify installation in dense panels. It’s well suited for motor feeders and transformer protection in automation environments where uptime and predictable tripping matter.
Electrical durability is rated at 8000 cycles per hour and mechanical durability at 25,000 cycles, supporting frequent switching without premature wear. Combined with a modest weight and compact footprint, this reduces maintenance time and inventory while sustaining reliable protection.