ABB 1SDA067913R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA067913R1
Quick Summary
ABB 1SDA067913R1 Moulded Case Circuit Breaker is a protective device that interrupts fault currents in low-voltage distribution panels. Engineers often struggle with nuisance trips and rising maintenance costs when selecting reliable breakers for motor feeders and power distribution. This XT2 family member is IEC 60947-2 compliant, CE marked, and documented under ETIM 8 to simplify procurement and reporting. With a front-terminal 4P design, 690 V capability, and a 160 A rating, it delivers dependable protection while enabling installation efficiency and lower total cost of ownership for LV panels.
Product Information
Extended Description
1SDA067913R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 160 A FULLY RATED NEUTRAL
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
e03cc16a-56e7-4aed-a893-2a4e3eca5675 China (CN)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE4160GFF000XXX
EAN
8015644018092
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644018092
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
GL Certificate
1SDL000163R0093
LR Certificate
LRs certificate Tmax XT
UL Certificate
No certification needed
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, fixed XT2 4P design reduces wiring errors and installation time, delivering a cleaner panel layout and faster commissioning in motor feeder applications. The business impact is measurable through reduced field labor and fewer miswiring incidents, improving first-time hit rates in panel builds. This supports sectors like packaging, process automation, and material handling where space and uptime matter. Ekip LSIG release provides precise, reliable tripping under fault conditions, decreasing arc flash exposure and operator risk while protecting critical loads in distribution boards. With a 160 A rating at 690 V, feeders are safeguarded from overloads and short circuits, lowering unplanned downtime and extending equipment life. The busbar connection accommodates 32.5 to 100 mm² cross-sections, enabling quick retrofits and compatibility with common rack designs, which reduces inventory complexity for integrators. Durability specs—up to 8,000 electrical cycles and 25,000 mechanical cycles—translate into predictable lifecycle performance and lower maintenance costs for industrial facilities. Compliance with IEC 60947-2, RoHS, REACH and CE declarations, along with the 55.70% recyclability rate per EN45555, supports sustainable operation and regulator-ready documentation. The 1.6 kg body promotes manageable installation in compact switchgear while handling mounting and front-termination advantages, streamlining service tasks and upgrades across existing LV networks.
Get a Quick Quote for a ABB 1SDA067913R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA067913R1?
Enquire Now
FAQs
For installation, ensure front-terminal accessibility and correct torque of 6 N·m on each bolt. Use a busbar cross-section in the 32.5–100 mm² range and secure the unit to a compliant panel mounting frame. Verify conductor insulation, tighten per the specified torque, and confirm alignment with IEC 60947-2 requirements to minimize future maintenance.
The device provides a rated service short-circuit breaking capacity up to 100 kA depending on voltage, with a 690 V rated operational voltage and 8 kV impulse withstand. In practical terms, it safely interrupts high-energy faults on LV feeders, reducing damage to downstream equipment and enabling quicker restoration after a fault.
Yes. It features a robust front-terminal design with solid-state release Ekip LSIG, designed to respond quickly to overloads and short circuits in motor feeders. The 4P configuration supports multi-pedestal protection, and the 690 V rating ensures compatibility with typical LV motor starter circuits, while the compact XT2 form factor fits tight switchgear layouts.
The product is CE compliant with EC Declaration of Conformity for Tmax XT2, and adheres to RoHS and REACH standards. It also aligns with EN45555 for recyclability (55.70%) and provides relevant environmental data in the EPD. UL/VDE certifications are listed as not required for this model but confirm ongoing regulatory alignment.
ROI is driven by reduced maintenance and uptime improvements. The front-terminal design speeds installation, while LSIG release enhances fault protection, decreasing unplanned outages. The 160 A rating and high Ics/Icu ratings enable safer, longer-lasting feeders, lowering replacement costs and extending service intervals in factory floors and process plants.