ABB 1SDA069448R1 Moulded Case Circuit Breaker - 8 kV
Part Number: 1SDA069448R1
Quick Summary
ABB 1SDA069448R1 Moulded Case Circuit Breaker protects 3-phase power distribution in industrial equipment. When space is tight or downtime looms, you need a compact, reliable protection device with front terminals for fast maintenance. Certified to IEC standards with CE conformity and RoHS compliance, this unit also supports CMRT and TSCA declarations for safer, compliant installations. With an 800 A rating and 690 V operating capability, plus an 8 kV impulse withstand, it helps maximize uptime while meeting stringent safety requirements. Designed for Tmax T7 compatibility and 3P front-terminal mounting, it streamlines panel wiring and simplifies installation across global facilities. This combination of performance, compliance, and serviceability translates into lower risk, faster commissioning, and sustained production throughput.
Product Information
Extended Description
1SDA069448R1 ABB: C.BREAKER TMAX T7X 800 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR332/P-LSI R 800
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T7 | Breakers - Packaging disposal information
EAN
8015644701284
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
154 mm
Product Net Weight
9.7 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
280 mm
Package Level 1 Height
350 mm
Package Level 1 Depth / Length
360 mm
Package Level 1 Gross Weight
11.2 kg
Package Level 1 EAN
8015644701284
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T7
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
3000 cycle | 60 cycles per hour
Mechanical Durability
10000 cycle | 60 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 32 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 170 kA | (230 V AC) 170 kA | (380 V AC) 170 kA | (400 V AC) 170 kA | (415 V AC) 170 kA | (440 V AC) 170 kA | (500 V AC) 170 kA | (690 V AC) 75 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 170 kA | (230 V AC) 170 kA | (380 V AC) 170 kA | (400 V AC) 170 kA | (415 V AC) 170 kA | (440 V AC) 170 kA | (500 V AC) 170 kA | (690 V AC) 75 kA
Rated Uninterrupted Current (Iu)
800 A
Release
PR332/P LSI
Release Type
EL
Short-Circuit Performance Level
X
Standards
IEC
Sub-type
T7
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
9AKK105713A5946
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T7
Wiring Diagram
Wiring diagram T7-T7M
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P front-terminal design enables quick wiring and safer maintenance. Business Impact: Reduces installation time and minimizes live-work risk for technicians. Application: Ideal for main feeders in manufacturing lines and transformer protection in harsh industrial environments. Feature: Rated 800 A with 690 V AC operation and Ui 1000 V insulation. Business Impact: Delivers robust protection for high-load drives and motors while sustaining selective coordination. Application: Suitable for large MCCB installations in complex panels. Feature: Ics up to 170 kA and Icu up to 170 kA at multiple voltages. Business Impact: Provides strong fault current resistance, improving equipment safety and uptime. Application: Panels near transformers and generators in energy-intensive facilities. Feature: Release PR332/P LSI with front-mounted operation for quick actuation and safer service. Business Impact: Improves maintenance access and reduces downtime during fault testing. Application: Tmax T7 family panels with front-terminal architecture. Feature: Compliance and sustainability through RoHS, CE, CMRT, and TSCA declarations. Business Impact: Eases regulatory approvals and supply-chain risk management. Application: Global deployments with strict environmental and material controls. Feature: Mechanical durability 10000 cycles and electrical durability 3000 cycles (60 cycles/hour) ensure long service life. Business Impact: Lower replacement and maintenance costs across the equipment lifecycle. Application: Continuous-duty protection in demanding industrial settings.
Get a Quick Quote for a ABB 1SDA069448R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA069448R1?
Enquire Now
FAQs
Begin with panel clearance and safety lockout, then remove the terminal cover to expose front-terminal access. Use proper torque for the fixed front terminals, verify correct phasing, and route conductors neatly. Confirm the device is seated fully in the panel enclosure and perform a functional test after wiring to ensure dependable protection and easy future maintenance.
The MCCB delivers a rated service short-circuit breaking capacity Ics up to 170 kA and a rated ultimate short-circuit breaking capacity Icu of up to 170 kA at 690 V, with compatibility across 220–440/690 V systems. This supports strong fault-current resistance while enabling selective coordination with upstream protective devices.
Yes. The product includes a CE Declaration of Conformity and RoHS compliance documentation. It also provides CMRT and TSCA declarations, supporting global regulatory and sustainability requirements for electronics and electrical components.
This 3P MCCB is designed for Tmax T7 panels and main feeder protection in industrial plants, featuring front-terminal mounting for straightforward wiring and an 800 A rating to support large motors and transformers while enabling quick replacements during maintenance windows.
Electrical durability is rated at 3000 operating cycles and mechanical durability at 10000 cycles (60 cycles per hour). This translates to longer service life, reduced replacement intervals, and lower total cost of ownership in demanding production environments.