ABB 1SDA074679R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA074679R1
Quick Summary
ABB Tmax XT1 1SDA074679R1 is a four-pole molded case circuit breaker for industrial power distribution and transformer protection. This design helps reduce nuisance trips and simplifies front-terminal wiring, addressing common downtime and maintenance costs. It carries UL489/CSA certifications with CE conformity, plus environmentally conscious declarations (EPD, RoHS, REACH) that support sustainable asset management. For panel builders and service teams, the XT1S delivers predictable protection with easy installation, compatibility with busbar connections from 45.5 to 80 mm², and robust environmental compliance, enabling safer, more efficient operations while meeting regulatory requirements.
Product Information
Extended Description
1SDA074679R1 ABB: C.BREAKER TMAX XT1S 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 15-500 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SU4015AFF000XXX
EAN
8015644786564
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644786564
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.1 W
Rated Current (In)
15 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
15 A
Short-Circuit Performance Level
S
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 35 kA | (600Y / 347 V AC) 22 kA | (250 V DC) 2 Poles in Series 42 kA | (500 V DC) 4 Poles in Series Kind 50 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3905
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
UL Certificate
1SDL000163R0111
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1 UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Front-terminal, bolt-type terminals enable clean, fast wiring and reliable high-density mounting, reducing installation time and field faults in control panels and switchgear. This translates to lower labor costs and enhanced panel reliability in harsh industrial environments. Feature → TMF thermo-magnetic release combined with a 4P XT1 design provides precise overcurrent protection with a trusted response time, minimizing downstream equipment damage and downtime during fault events in transformer feeders and distribution boards. Feature → Rated 15 A with a 600Y/347 V AC, 500 V DC rating and 125 A Iu support, delivering scalable protection for mid-range power circuits while maintaining safe operating margins in variable loads typical of industrial plants. Feature → Front-terminal connection type and bolt terminal design offer easy field maintenance and re-wiring, improving serviceability in retrofit projects and new installations alike. Feature → High interrupting ratings (UL489) up to 65 kA at 240 V and 42–50 kA for DC configurations provide headroom for short-circuit events, enabling design engineers to consolidate protection strategies without over-specifying devices. Feature → Compliance and environmental data (EPD, RoHS, REACH, CMRT) support corporate sustainability goals and regulatory adherence, reducing lifecycle risk and improving supplier risk management in procurement processes. Feature → Compact dimensions (101.6 mm W x 130 mm H x 70 mm D) and 1.4 kg weight simplify enclosure layouts and allow faster panel assembly, benefiting OEMs and MRO teams during install and service. Feature → Clear documentation (wiring diagram, mechanical drawings, dimension diagrams) fosters accurate installation and reduces field modification time, improving overall project timelines and compliance.
Get a Quick Quote for a ABB 1SDA074679R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA074679R1?
Enquire Now
FAQs
Install with front terminals using bolt connections and a recommended screwdriver size M6. Tighten to 6 N·m and follow the XT1 wiring diagram for XT1, XT2, XT3, and XT4 configurations to ensure proper fault protection and serviceability.
Rated current is 15 A; rated operating voltage is 600Y/347 V AC and 500 V DC; its rated short-circuit instantaneous setting Ii is 500 A, while the rated uninterrupted current Iu is 125 A. Interrupting ratings per UL489 include 65 kA at 240 V AC, 35 kA at 480 V AC, and 22 kA at 600Y/347 V AC, with higher DC ratings for series connections.
Yes. It is a UL489/CSA certified Tmax XT XT1 device with CE conformity, designed for UL/CSA panel protection and compliant with ABB Sace Tmax XT class requirements, including front-terminal installation and TM release features for reliable distribution protection.
Certifications include UL Certificate 1SDL000163R0111, CE Declaration of Conformity, and CSA approvals. Environmental and compliance documents include EPD for Tmax XT XT1, RoHS Declaration, REACH Declaration, CMRT, TSCA declaration, and end-of-life disassembly instructions consistent with ABB EcoSolutions.
Product dimensions are 101.6 mm wide, 130 mm high, and 70 mm deep, with a net weight of 1.4 kg. Packaging (box) units are 1 piece per carton with inline dimensions. These specs support enclosure fitment and mounting clearances in control cabinets.