ABB 1SDA074687R1 Moulded Case Circuit Breaker - UL/CSA

Part Number: 1SDA074687R1
Manufacturer
ABB
Part number
1SDA074687R1

Quick Summary

ABB 1SDA074687R1 Moulded Case Circuit Breaker protects power circuits in industrial control panels. When loads vary or surges occur, operators need reliable, trip-accurate protection that minimizes downtime and simplifies maintenance. This XT1 4P device delivers UL489/CSA compliance and CE conformity, backed by UL certification and RoHS declarations, helping you meet global standards with confidence. By combining compact form factor with front-terminal accessibility, it reduces installation time and cabinet congestion. The result is safer commissioning, lower energy waste from nuisance trips, and better lifecycle cost control for panel builders, machine builders, and system integrators alike.

Product Information

Extended Description

1SDA074687R1 ABB: C.BREAKER TMAX XT1S 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 60-600 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SU4060AFF000XXX
EAN
8015644786649
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644786649
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.9 W
Rated Current (In)
60 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
700 A
Rated Operational Voltage
600Y/347 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
60 A
Short-Circuit Performance Level
S
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 65 kA | (480 V AC) 35 kA | (600Y / 347 V AC) 22 kA | (250 V DC) 2 Poles in Series 42 kA | (500 V DC) 4 Poles in Series Kind 50 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3905
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
UL Certificate
1SDL000163R0111
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1 UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P XT1 frame with TMF release and fixed front terminals delivers precise protection for demanding automation environments, reducing unexpected outages and enabling predictable downtime planning. This translates to improved line availability and faster changeovers in production lines, transformers, and distribution boards. Application: Power distribution and automation panels benefit from tighter protection schemes and easier maintenance planning. Feature → Business Impact → Application: Rated current of 60 A with an uninterrupted current rating of 125 A and a robust instantaneous setting of 700 A provides a balance between selectivity and protection for varied load profiles. Benefit: minimizes nuisance trips while preserving safety, lowering scrap and rework in manufacturing and processing facilities. Application: Motor feeders, machine bays, and control cabinets in manufacturing lines. Feature → Business Impact → Application: Front-terminal bolt connections with a 6 N·m tightening torque and busbar compatibility of 45.5 to 80 mm² streamline field wiring and reduce installation time. Benefit: faster, more reliable commissioning and easier future upgrades or reworks. Application: Dense panel interiors, new-builds, and retrofits. Feature → Business Impact → Application: UL489/CSA certification, CE conformity, and RoHS declarations simplify global procurement and compliance audits. Benefit: enables cross-border projects with fewer qualification hurdles and lower regulatory risk. Application: International rollout of power distribution architectures in OEMs and integrators. Feature → Business Impact → Application: End-of-life and disassembly guidance, together with environmental declarations (EPD, 55.9% recyclability) support sustainable asset retirement. Benefit: reduces total cost of ownership and supports corporate sustainability targets. Application: Plant lifecycle management and decommissioning projects.

Get a Quick Quote for a ABB 1SDA074687R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA074687R1? Enquire Now

FAQs

Follow the installation instructions: mount in a compliant enclosure, connect the busbar within the 45.5–80 mm² range, secure front-terminal bolts, and tighten to 6 N·m. Use the M6 main circuit screwdriver as recommended and verify 600Y/347 V rating during commissioning.
It adheres to UL489 and CSA CS22.2 standards, carries a UL certificate (1SDL000163R0111), and provides a CE Declaration of Conformity, along with RoHS declarations for regulatory clarity.
Ideal for power distribution in industrial control panels, transformers, and motor feeders. With a 60 A rating and TMF release, it supports reliable protection while accommodating diverse load profiles common in automation and process industries.
Rated current is 60 A; rated voltage is 600Y/347 V AC (and 500 V DC); Iiu is 125 A; instantaneous setting Ii is 700 A; number of poles is 4P; terminal type is front bolt; and tightening torque is 6 N·m.
Disassembly instructions for Tmax XT XT1 are provided, along with an Environmental Product Declaration (EPD) and recyclability data (55.9%); these aid sustainable disposal and reuse planning at end-of-life.