ABB 1SDA074696R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA074696R1
Quick Summary
Moulded Case Circuit Breaker is a protection device that safeguards industrial power circuits in distribution panels and machinery. When integrated with SACE Tmax XT XT1 technology, it delivers precise overload and short‑circuit protection for demanding environments. A common challenge is selecting a device that meets UL489/CSA listings while fitting front-terminal mounting and compact form factors. This ABB XT1 family product combines a 3-pole configuration, 25 A rated current, and a 600Y/347 V rating with TMF release, delivering reliable tripping under fault conditions. Its ECO-Solutions data, RoHS/REACH compliance, and end-of-life guidance support sustainability programs. For procurement teams, this translates to lower engineering rework, easier compliance documentation, and reduced total cost of ownership through standardization with Tmax XT.
Product Information
Extended Description
1SDA074696R1 ABB: C.BREAKER TMAX XT1H 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 25-500 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HU3025AFF000XXX
EAN
8015644786731
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8015644786731
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.0 W
Rated Current (In)
25 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
25 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA | (480 V AC) 65 kA | (600Y / 347 V AC) 25 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 4 Poles in Series Kind 50 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3905
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
UL Certificate
1SDL000163R0111
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1 UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3-pole XT1 molded case design provides centralized protection for three-phase power feeders, reducing wiring complexity and enabling faster fault isolation in panelboards and motor control centers. This translates to improved reliability and easier maintenance in manufacturing lines and process plants. The 25 A rated current with a configurable setting range ensures precise protection tailored to load profiles, minimizing nuisance trips and downtime in control circuits and small switchgear. The front-terminal, bolt-type connection supports quick installation and straightforward retrofits in existing cabinets, lowering commissioning time and enabling scalable distribution in new builds or expansions. With a rated operational voltage of 600Y/347 V AC and 500 V DC, it covers a wide range of industrial power systems, reducing the need for multiple device families. The TMF release and fast opening time of 30 ms deliver rapid fault clearance, enhancing personnel safety and protecting downstream equipment in conveyors and machinery lines. Durable electrical and mechanical performance—120 cycles per hour/8000 cycles and 240 cycles per hour/25000 cycles—addresses reliability expectations for high‑demand environments, supporting longer life in repetitive switching applications. RoHS and REACH compliance, plus end-of-life disassembly instructions, support sustainability programs and regulatory reporting for OEMs and end users. Overall, the device contributes to reduced total cost of ownership through standardized XT protection, easier regulatory documentation, and improved field service efficiency.
Get a Quick Quote for a ABB 1SDA074696R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA074696R1?
Enquire Now
FAQs
The 1SDA074696R1 is designed for front‑terminal, bolt‑connected installation in 3P XT1 configurations and fits standard low‑voltage switchgear and panelboards used in industrial facilities. Its 600Y/347 V rating supports typical distribution panels and motor control centers.
It is a 3‑pole device with a 25 A nominal current rating, a 25 A setting range, and a rated instantaneous short‑circuit current setting (Ii) of 500 A. It supports rated operating voltage of 600Y/347 V AC and 500 V DC, with a front‑mounted TMF release for precise tripping.
Yes. It carries UL489/CSA certification and a CE Declaration of Conformity for Tmax XT XT1 products, ensuring compliance for global electrical installations. This supports regulatory documentation and contractor acceptance in many regions.
Front terminals with bolt connections simplify wiring and enable faster installation or replacement in existing cabinets. Tightening torque is specified at 6 N·m, and a recommended main circuit screwdriver is M6, facilitating quick field service and reliable connections.
The device includes End Of Life disassembly instructions, an Environmental Product Declaration (EPD) for Tmax XT XT1, and a design for closing resource loops per EN45555. Recyclability is rated at 55.9%, helping equipment manufacturers meet green procurement targets and regulatory reporting requirements.