ABB 1SDA074709R1 Moulded Case Circuit Breaker - UL/CSA

Part Number: 1SDA074709R1
Manufacturer
ABB
Part number
1SDA074709R1

Quick Summary

The ABB 1SDA074709R1 is a molded case circuit breaker designed to protect low‑voltage distribution in industrial panels. This delivers reliable overcurrent protection while simplifying wiring in compact switchgear, reducing installation time and risk of miswiring. It carries key certifications such as UL489, CSA, and CE conformity, ensuring regulatory compliance across North American and European projects. With front-terminal accessibility and TMF release, it supports efficient maintenance, selective tripping, and robust performance in demanding environments, while aligning with ABB’s Tmax XT heritage. For engineers seeking dependable protective devices that fit 600Y/347V systems and compact power distribution layouts, this MCCB offers clear value in lifecycle cost, uptime, and safety while remaining compatible with SACE Tmax XT components.

Product Information

Extended Description

1SDA074709R1 ABB: C.BREAKER TMAX XT1H 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 15-500 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HU4015AFF000XXX
EAN
8015644786861
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644786861
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.1 W
Rated Current (In)
15 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
15 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA | (480 V AC) 65 kA | (600Y / 347 V AC) 25 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 4 Poles in Series Kind 50 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3905
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
UL Certificate
1SDL000163R0111
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1 UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P XT1H design with front terminals enables faster wiring and cleaner panel layouts, improving installation efficiency and reducing field labor costs in distribution panels for transformers and motor control centers. This translates to measurable time savings during commissioning and easier future maintenance in brownfield sites. The rated current of 15 A with a rated operational voltage of 600Y/347 V AC (and 500 V DC) supports compact, energy-efficient power distribution for small machinery and control circuits, delivering predictable protection without oversizing components. The TMF release mechanism provides reliable thermal-magnetic protection with a setting range around 15 A, improving selectivity and reducing nuisance trips in busy industrial environments. The 4P configuration, front terminals, and bolt-type connections paired with a 6 N·m tightening torque enable solid, vibration-resistant connections in panel boards and switchgear. With a busbar compatibility range of 45.5 to 80 mm², installers can reuse existing busbars and standardize across multiple panels. The device’s robust UL489 interrupting ratings (up to 100 kA at 240 V, 65 kA at 480 V, 25 kA at 600Y/347 V) ensure protection for both feeders and transformer feeds under fault conditions. Its compact dimensions (101.6 mm W × 130 mm H × 70 mm D) and weight (1.4 kg) facilitate easy rack mounting and scalable protection in modular assemblies. The unit’s low power loss (about 1.1 W per pole) supports energy-efficient protection schemes in continuously energized systems. ABB’s environmental declarations, including EPD, RoHS, REACH, and CMRT, support sustainability reporting and regulatory compliance for modern projects. In scenarios demanding high reliability and compliance, the XT1H 125 TMF delivers a proven solution that minimizes downtime and simplifies lifecycle management.

Get a Quick Quote for a ABB 1SDA074709R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA074709R1? Enquire Now

FAQs

Install the XT1H 125 TMF in a compatible panel using the front-terminal connections. Use a M6 screwdriver for main circuit terminals, tighten to 6 N·m, and ensure the busbar section is within 45.5 to 80 mm². Verify the device is oriented for accessible wiring and that assembly conforms to UL489 and local electrical codes.
For 600Y/347 V AC, the interrupting rating is up to 25 kA, with higher ratings available at other voltages (240 V AC up to 100 kA; 480 V AC up to 65 kA). These values ensure adequate fault protection for feeders and transformer feeds in industrial installations.
Yes. The device is part of the SACE Tmax XT family designed for low‑voltage transformer and distribution protection with four poles, front terminals, and TMF release, delivering reliable overcurrent protection for transformer feeders and associated switchgear in industrial environments.
The MCCB carries UL489 and CSA certifications, plus a CE Declaration of Conformity. It also aligns with RoHS and REACH declarations, CMRT for conflict minerals, and other ABB EcoSolutions commitments for lifecycle and sustainability reporting.
TMF (Thermal-Magnetic) release provides precise overcurrent protection with defined trip curves, improving selectivity and reducing nuisance trips. The unit supports robust operating and mechanical durability metrics, enabling predictable performance across frequent switching cycles in demanding industrial applications.