ABB 1SDA074711R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA074711R1
Quick Summary
ABB 1SDA074711R1 Moulded Case Circuit Breaker protects distribution panels in low-voltage power systems. It addresses downtime and nuisance trips by delivering precise protection with front-terminal access for quick maintenance. This XT Tmax XT product carries UL489 and CSA certifications, along with CE conformity and RoHS/REACH compliance, supporting global deployment. By aligning with the TMF release and XT1 family, it delivers scalable protection, simplified installation, and long-term reliability for engineers and procurement teams aiming to optimize uptime and lifecycle costs.
Product Information
Extended Description
1SDA074711R1 ABB: C.BREAKER TMAX XT1H 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 25-500 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HU4025AFF000XXX
EAN
8015644786885
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644786885
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.0 W
Rated Current (In)
25 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
25 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA | (480 V AC) 65 kA | (600Y / 347 V AC) 25 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 4 Poles in Series Kind 50 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3905
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
UL Certificate
1SDL000163R0111
VDE Certificate
No certification needed
Dimension Diagram
XT1 3p-4p fixed front terminals
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1 UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole XT1 chassis with TMF release ensures precise coordination across multi-line feeders. Business Impact: Reduces fault propagation and maintenance complexity, boosting line availability in industrial plants. Application: Power distribution panels, motor feeders, and transformer protection. Feature: Front-terminal connection and bolt terminals with a 6 N·m tightening torque. Business Impact: Faster, safer field wiring and repeatable torque quality, improving install times and device longevity. Application: Panel builders and OEM switchgear assembly. Feature: Rated current 25 A with rated operational voltage 600Y/347 VAC and DC 500 V. Business Impact: Clear, predictable protection for mixed AC/DC loads, enabling compliant design with high fault tolerance. Application: Controls for conveyors, pumps, and light industrial automation. Feature: High UL489 interrupting ratings up to 25 kA at 600Y/347 VAC and DC ratings up to 50 kA in series. Business Impact: Enhanced fault-handling capability and system resilience. Application: Transformer and distribution feeder protection where fault currents are a concern. Feature: Power loss (2.0 W per pole) and compact XT1 footprint. Business Impact: Lower energy consumption and easier heat management in dense panel layouts. Application: Critical control panels with space and energy budgets. Feature: Compliance and sustainability credentials (RoHS/REACH, CMRT, TSCA, EPD). Business Impact: Regulatory assurance and responsible sourcing with easier end-of-life planning. Application: Global deployments with strict environmental and material declarations. Feature: Comprehensive installation data (busbar 45.5–80 mm², front connections, M6 driver). Business Impact: Streamlined installation, verified reliability, and rapid commissioning. Application: Industrial panels, switchgear assemblies, and field retrofits.
Get a Quick Quote for a ABB 1SDA074711R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA074711R1?
Enquire Now
FAQs
This 4P XT1 device uses front-terminal bolt connections designed for SACE Tmax XT assemblies. It supports busbar connections from 45.5 to 80 mm², requires a Main Circuit M6 screwdriver, and tightens to 6 N·m, matching standard ABB panel-builder practices for rapid, reliable integration.
Rated current is 25 A with a rated operational voltage of 600Y/347 VAC and 500 V DC. It provides an uninterrupted current (Iu) of 125 A and a short-circuit instantaneous setting (Ii) of 500 A, with UL489 interrupting ratings up to 25 kA at 600Y/347 VAC and 50 kA for certain DC configurations in series.
Yes. It carries RoHS and REACH declarations, CMRT for conflict minerals, and TSCA declarations. An Environmental Product Declaration (EPD) is available for Tmax XT XT1, and design supports a 55.9% recyclability rate per EN45555.
Certification set includes UL Certificate 1SDL000163R0111, CSA Certificate 9AKK10103A3905, CE DoC for Tmax XT1, and VDE status indicating broader compliance. Data sheets and installation manuals are available (XT1 UL/CSA docs).
With front-terminal access, TMF release for reliable coordination, and clear End-of-Life disassembly instructions, maintenance cycles shorten and uptime improves. Disassembly and recycling guidance, packaging disposal information, and a recyclable design help lower total cost of ownership over the system’s life.