Quick Summary

ABB 1SDA074816R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for power distribution panels in industrial environments. This four-pole XT2 device integrates front terminals and a TMA release for fast, safe operation. Use it to minimize nuisance trips, improve maintenance efficiency, and simplify retrofits in harsh conditions. The product carries UL489/CSA listings and CE declarations, reflecting compliance with key safety and performance standards. Additional lifecycle data—EPD, recyclability, and end-of-life instructions—supports sustainable procurement. As part of the SACE Tmax XT family, it delivers familiar protection characteristics and scalable settings, helping engineers consolidate spare parts and reduce total cost of ownership while meeting project timelines.

Product Information

Extended Description

1SDA074816R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 125 I3=625...1250 A FULLY RATED NEUTRAL
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HU4125BFF000XXX
EAN
8015644787936
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.55 kg
Package Level 1 EAN
8015644787936
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
625…1250 A
Rated Operational Voltage
600 V AC | 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA | (480 V AC) 65 kA | (600 V AC) 25 kA | (250 V DC) 2 Poles in Series 65 kA | (500 V DC) 3 Poles in Series 65 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3906
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | Release assembly XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Four-pole XT2 design with front-terminal connections. Business Impact: Faster wiring, simpler panel integration, and reduced field assembly time. Application: New panel builds or retrofits in manufacturing lines where space is constrained. Feature: Rated current of 125 A with an adjustable setting range of 87.5 to 125 A and a wide short-circuit current setting from 625 to 1250 A. Business Impact: Precise protection Coordination, minimizing unnecessary trips and enabling selective protection strategies. Application: feeders and distribution blocks in process plants and data centers. Feature: Rated voltage of 600 V AC and 500 V DC with 4P operation. Business Impact: Single device covers mixed AC/DC loads, reducing part count and simplifying inventory. Application: motor drives, control circuits, and DC power rails. Feature: Release type TMA with TM setting options and a 30 ms opening time. Business Impact: Fast, predictable breaking behavior and improved protection selectivity. Application: critical feeder protection where speed matters. Feature: Power loss of 11.4 W per pole and compact footprint (120 × 130 × 82.5 mm). Business Impact: Lower heat generation and cooler panels, enabling denser layouts and longer service intervals. Application: space-constrained control panels in factory automation. Feature: Front terminal connection, compatible busbar range 32.5–100 mm², tightening torque 6 N·m. Business Impact: Reliable, field-friendly wiring with repeatable torque for consistent performance. Application: panel assemblies and cabinet wiring. Feature: UL489 and CSA compliance, CE Declaration, and lifecycle data (EPD, recyclability). Business Impact: Regulatory confidence, streamlined procurement, and sustainability alignment. Application: procurement for regulated industries pursuing green certifications and end-of-life planning.

Get a Quick Quote for a ABB 1SDA074816R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA074816R1? Enquire Now

FAQs

ABB 1SDA074816R1 uses a front-terminal XT2 format and 4P configuration, designed for straightforward retrofit into existing panels. It supports busbars from 32.5 to 100 mm² and requires a tightening torque of 6 N·m, ensuring reliable, repeatable connections. This compatibility minimizes wiring changes and speeds up commissioning in upgrades.
Verify rated current of 125 A, adjustable I_i range of 625–1250 A, rated voltage of 600 V AC / 500 V DC, and four-pole front-terminal construction. Confirm declaration of conformity and UL/CSA listings, including UL certificate 1SDL000163R0112 and CSA certificate 9AKK10103A3906, to ensure regulatory compliance for the target installation.
Industrial manufacturing lines, process industries, and data center power distribution benefit most, where reliable overcurrent protection and swift fault clearing are essential. Applications include feeders for motors, drives, and mixed AC/DC circuits, with space-constrained panels requiring compact, modular protection devices from the SACE Tmax XT family.
This model carries UL489 and CSA certifications, CE declaration of conformity, UL certificate 1SDL000163R0112, and RoHS/REACH declarations. It also provides environmental data such as EPD and 55.70% recyclability per EN45555. These certifications streamline procurement and support sustainability and compliance in regulated markets.
Maintenance revolves around periodic inspection of terminal connections (6 N·m torque), cleaning of front-terminal interfaces, and monitoring heat rise in panels due to 11.4 W per pole losses. ROI benefits come from reduced downtime, lower panel heat, streamlined spare parts inventory, and alignment with end-of-life recycling programs, thanks to the device’s environmental data and reusable components.