ABB 1SDA075023R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA075023R1
Quick Summary
Moulded Case Circuit Breaker ABB 1SDA075023R1 protects industrial power distribution by interrupting fault currents in switchgear. Maintenance downtime and costly replacements rise when breakers fail to trip reliably or meet UL/CSA standards. This device carries UL489/CSA certification, CE conformity, and RoHS/REACH declarations to support global installations. As part of the SACE Tmax XT family, it supports front-terminal mounting for quick service and safer maintenance. Designed for 690 V systems with 100 A rating and 1000 V insulation, it aligns with common industry practices while enabling streamlined procurement and lifecycle planning for electrical engineers and procurement teams.
Product Information
Extended Description
1SDA075023R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 100 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HU3100GFF000XXX
EAN
8015644790004
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644790004
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.20 W
Rated Current (In)
100 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 A | (480 V AC) 65 A | (600 V AC) 25 A
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3906
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Three-pole XT2 design with fixed front terminals and 100 A rating. Business Impact: Provides reliable three-phase protection while simplifying installation in standard distribution panels. Application: Suited for 3P protection in switchgear and MCCs, minimizing wiring complexity and shortening commissioning time. Long-tail keywords: 3P molded case breaker, front-terminal MTX XT2, 100 A MCCB. Benefit: Reduces wiring errors and accelerates panel assembly in industrial environments. Feature: UL489/CSA certifications, CE conformity, RoHS/REACH compliance. Business Impact: Ensures regulatory compliance across North America and Europe, reducing risk during audits. Application: Ideal for global projects requiring cross-border approvals and traceable material declarations. Long-tail keywords: UL489 listed breaker, CE compliant MCCB, RoHS compliant SACE Tmax XT. Benefit: Simplifies procurement and supports sustainability reporting. Feature: High durability ratings—electrical 8000 cycles; mechanical 25000 cycles. Business Impact: Extends service life and lowers maintenance costs by reducing premature replacements. Application: Fits high-usage environments such as data centers, manufacturing lines, and critical power feeders. Long-tail keywords: high-cycle MCCB, electrical durability 8000 cycles, mechanical durability 25000 cycles. Benefit: Improves system uptime and total cost of ownership. Feature: Rated Insulation Voltage Ui 1000 V and Rated Operational Voltage 690 V. Business Impact: Enables safe operation in high-voltage distribution networks without oversized devices. Application: Protective devices for transformers, feeders, and busbars in medium- and high-voltage panels. Long-tail keywords: 1000 V Ui, 690 V Ur, high-voltage protection. Benefit: Enhances safety margins and design flexibility. Feature: Front-terminal connection and 6 N·m tightening torque with M6 screwdriver. Business Impact: Simplifies field wiring and delivers repeatable, reliable terminations. Application: Useful in cramped or modular switchgear where torque control is critical. Long-tail keywords: front terminal MCCB installation, 6 N·m torque, M6 screwdriver. Benefit: Reduces installation time and torque errors. Feature: Compact dimensions and weight (90 mm W x 130 mm H x 82.5 mm D; 1.2 kg). Business Impact: Facilitates panel mounting in restricted spaces and lowers shipping costs. Application: Suitable for compact switchgear and retrofit projects with limited clearance. Long-tail keywords: compact molded case breaker, lightweight 1.2 kg MCCB, space-saving protection device. Benefit: Improves fit and logistics efficiency.
Get a Quick Quote for a ABB 1SDA075023R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA075023R1?
Enquire Now
FAQs
The device supports 3P front-terminal connections and busbar ranges of 32.5 to 100 mm², with a rated operational voltage of 690 V AC and Ui of 1000 V; it fits standard 690 V switchgear and distribution panels, enabling straightforward retrofits and new installs without bespoke hardware or adapters.
UL489 certification covers performance in North American equipment, while CSA listing confirms compliance in Canadian installations. This product also presents CE conformity, RoHS and REACH declarations, and intrinsic safety facets for certain configurations, helping you meet multi-region regulatory demands and sustainability reporting.
Yes. The XT2 3P model is designed for three-pole protection with fixed front terminals, rated at 100 A and 690 V operating voltage. It's engineered for reliable tripping with fast opening times, making it suitable for distribution boards, MCCs, and transformer protection in industrial environments.
With electrical durability rated at up to 8000 cycles and mechanical durability up to 25000 cycles, the breaker minimizes replacement costs and downtime. Its RoHS/REACH compliance supports sustainable builds, while the front-terminal design reduces maintenance time and simplifies field servicing, contributing to lower total cost of ownership.
Minimum Order Quantity is 1 piece, with packaging level 1 unit per box and EAN 8015644790004. US/Canada order code XT2HU3100GFF000XXX is provided for regional purchasing, along with Customs Tariff Number 85362090 to aid import processes and compliance.