ABB 1SDA075025R1 Moulded Case Circuit Breaker - UL/CSA
Part Number: 1SDA075025R1
Quick Summary
ABB 1SDA075025R1 Moulded Case Circuit Breaker protects power distribution panels and motor feeder lines. In busy plants, nuisance trips and wiring complexity slow upgrades and cut uptime. This UL489 and CSA listed device carries CE marking and RoHS/REACH compliance, supporting global approvals and supplier audits. With four front terminals, a 10 A rating, and 690 V AC capacity, it delivers reliable protection in compact enclosures. Designed for easy maintenance and quick replacement, it helps engineers balance safety, cost, and productivity across control panels.
Product Information
Extended Description
1SDA075025R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HU4010GFF000XXX
EAN
8015644790028
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644790028
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 A | (480 V AC) 65 A | (600 V AC) 25 A
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3906
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4934 >> 4 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Four-pole XT2 with front terminals and 10 A rated current reduces wiring footprint and simplifies panel assembly, delivering faster install times and consistent torque with 6 N·m tightening. This translates to lower labor costs and more reliable connections in power distribution and motor control applications. The UL489/CSA listing, together with CE marking and RoHS/REACH compliance, streamlines regulatory approvals and supplier audits, enabling easier deployment across multinational facilities. Interrupting ratings at 240 V, 480 V, and 600 V (up to 150 A, 65 A, and 25 A respectively) provide robust fault protection, reducing the risk of panel-wide failures and associated downtime. Electrical durability of 8000 cycles and mechanical durability up to 25,000 cycles support long service life in high-use environments. Front-terminal, bolt-type connections and a compact footprint (120 mm W × 130 mm H × 82.5 mm D) optimize cabinet real estate and simplify maintenance. Environmental and compliance data, including RoHS, REACH, CMRT, TSCA, and EPD, support sustainable procurement and end-of-life planning for responsible facilities.
Get a Quick Quote for a ABB 1SDA075025R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA075025R1?
Enquire Now
FAQs
ABB 1SDA075025R1 features four front terminals and a bolt connection type. Plan for a 6 N·m tightening torque on main circuit connections and ensure busbar sizing within 32.5 to 100 mm². The unit dimensions (120 mm wide, 130 mm high, 82.5 mm deep) fit standard 4-pole enclosures, supporting straightforward wiring and reliable, secure terminations during maintenance and replacement.
The device is rated for 10 A and 690 V AC, with 1000 V AC insulation voltage. Its UL489/CSA interrupting rating is (240 V AC) 150 A, (480 V AC) 65 A, and (600 V AC) 25 A, with an opening time around 30 ms depending on configuration. These specs enable safe fault clearance and protection for feeders and motors in industrial panels.
Yes. The 1SDA075025R1 is UL489 and CSA listed, supporting UL/CSA-labeled control panels and motor protection schemes. Its Ekip LSIG release and four-pole XT2 design provide reliable protection for 690 V systems, while front-terminal connections ease maintenance and replacement in manufacturing environments that require strict compliance and traceability.
This breaker complies with RoHS and REACH requirements, with CMRT, TSCA declarations, and an Environmental Product Declaration (EPD) available for Tmax XT XT2. Packaging disposal information is provided, supporting sustainable procurement. These declarations help with green采购 audits and regulatory reporting across global supply chains.
Electrical durability is rated at up to 8000 cycles (120 cycles per hour) and mechanical durability up to 25,000 cycles (25000 cycles). This translates to reduced replacement frequency and lower maintenance costs in high-use panels, improving uptime and total cost of ownership for mid- to large-scale protection schemes.