ABB 1SDA075072R1 Moulded Case Circuit Breaker - UL/CSA

Part Number: 1SDA075072R1
Manufacturer
ABB
Part number
1SDA075072R1

Quick Summary

1SDA075072R1 is a 3-pole molded-case circuit breaker designed for protecting 600 V AC power distribution in industrial control panels. Engineers often struggle to balance reliable protection with compact footprint in tight enclosures. UL489 listing and CSA certification, plus a CE declaration of conformity, underpin safe, compliant installations. Compatible with the SACE Tmax XT platform and ABB EcoSolutions approach, it supports efficient sourcing, testing, and lifecycle management. From a procurement perspective, the 1SDA075072R1 offers predictable lead times with a 1 piece MOQ and robust packaging. Its 60 A rating and 600 V AC capacity support reliable feeder protection for motors, transformers, and distribution panels.

Product Information

Extended Description

1SDA075072R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP M DIP I R 60 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HU3060JFF000XXX
EAN
8015644790493
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644790493
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.5 W
Rated Current (In)
60 A
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip M Dip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA | (480 V AC) 65 kA | (600 V AC) 25 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3906
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | Release Ekip G-LS/I, Ekip N-LS/I, Ekip M-LIU, Ekip M-I XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Three-pole XT2H construction with a 60 A rated current and 600 V AC capacity provides uniform protection across all phases. This reduces nuisance trips and improves uptime in machine frames and distribution panels. Ideal for motor feeders and transformer protection in industrial environments. Front-terminal design enables straightforward wiring and testing, while a fixed mounting footprint simplifies retrofits. This reduces commissioning time and minimizes field errors in crowded control cabinets. Compatible with busbar connections from 32.5 to 100 mm² and a tightening torque of 6 N·m for secure terminations, it supports reliable, vibration-tolerant connections in demanding environments. Release type Ekip M Dip I delivers a reliable, electronic release with fast opening times, typically around 30 ms for UL/CSA configurations. The result is rapid fault isolation and enhanced protection for critical loads such as conveyors, pumps, and presses. UL489 and CSA certifications, along with a CE declaration of conformity, enable global deployment across manufacturing sites while RoHS and REACH declarations reinforce material compliance in modern supply chains. ABB EcoSolutions features include End Of Life disassembly instructions and a documented recycling path, supporting responsible waste handling and regulatory reporting. Environmental data such as a 55.70% recyclability rate (EN45555) helps facilities meet sustainability targets. Electrical durability reaches up to thousands of cycles, while a mechanical durability profile up to tens of thousands of cycles ensures long service life in continuous operation. The unit’s compact footprint, weight of 1.12 kg, and front-terminal, bolt-type connections simplify installation and maintenance in compact switchgear or panel boards.

Get a Quick Quote for a ABB 1SDA075072R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA075072R1? Enquire Now

FAQs

Install the unit as a three-pole MCCB with front bolt terminals. Use busbar connections in the 32.5 to 100 mm² range and tighten to 6 N·m. The 60 A current rating and 600 V operating voltage suit most medium-load feeders, while the front-access design simplifies wiring and future testing.
The 1SDA075072R1 is rated for 60 A and 600 V AC. It provides UL489 and CSA listed protection with a 125 A Iu, and an interrupting rating of up to 150 kA at 240 V, 65 kA at 480 V, and 25 kA at 600 V, ensuring rapid fault clearance and reliable circuit protection in power distribution panels.
Yes. The 3P XT2H design supports motor feeders and transformer protection in industrial control environments. Its Ekip M Dip I release provides reliable tripping, and the front-terminal configuration facilitates clean wiring and testing for motor starters and small transformers in compact panels.
The device carries UL489 and CSA certifications, a CE declaration of conformity, and RoHS/REACH declarations. It also includes end-of-life information and disassembly instructions under ABB EcoSolutions, supporting regulatory compliance and sustainability reporting.
The unit offers robust mechanical durability and electrical durability with thousands of cycles, minimizing replacement frequency in continuous operation. Front terminals and modular design ease inspection and testing, while EcoSolutions data support recycling goals and lifecycle cost reduction in large-scale installations.