ABB 1SDA075073R1 Moulded Case Breaker - UL/CSA XT2H

Part Number: 1SDA075073R1
Manufacturer
ABB
Part number
1SDA075073R1

Quick Summary

ABB 1SDA075073R1 is a moulded case circuit breaker for industrial power distribution and motor protection. In compact switchgear, engineers often struggle with wiring access, installation time, and ensuring UL/CSA compliance. This unit meets UL489 and CSA CS22.2 standards with an EC CE declaration, and it’s part of the SACE Tmax XT ecosystem. Coupled with a front-terminal design, 3-pole configuration, and a 100 A rating, it streamlines panel builds and helps reduce downtime while improving safety. For buyers prioritizing reliability, easy installation, and regulatory conformity, this MCCB delivers robust protection with clear compatibility to modern control panels and drive systems.

Product Information

Extended Description

1SDA075073R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP M DIP I R 100 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HU3100JFF000XXX
EAN
8015644790509
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
131 mm
Package Level 1 Height
212 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8015644790509
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.2 W
Rated Current (In)
100 A
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip M Dip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA | (480 V AC) 65 kA | (600 V AC) 25 kA
ATEX Certificate
No certification needed
CSA Certificate (Intrinsic Safe)
9AKK10103A3906
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Dimension Diagram
XT2 3p-4p fixed front terminals
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | Release Ekip G-LS/I, Ekip N-LS/I, Ekip M-LIU, Ekip M-I XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The XT2H 3-pole moulded case breaker with front terminals simplifies wiring inside control panels, reducing installation time and risk of wiring errors, which translates to faster commissioning and safer maintenance in automation cabinets. This design supports front-access servicing while maintaining secure connections for demanding industrial environments, enabling quicker troubleshooting in production lines. Feature → Business Impact → Application: 100 A rated current and 600 V operating voltage provide dependable overcurrent protection for feeders and motor circuits, improving protection against insulation damage and nuisance trips in machine rooms and factory floors. This specification is ideal for panel builders and machine builders supplying conveyors, pumps, and presses where predictable protection improves uptime and maintenance planning. Feature → Business Impact → Application: Ekip M Dip I release and EL trip mechanism deliver precise, reliable tripping with fast response times, supporting critical safety requirements and reducing the risk of fault propagation in power distribution networks. Suitable for metal-cutting, packaging, and process automation lines where quick fault isolation minimizes downtime. Feature → Business Impact → Application: Electrical durability (up to 8000 cycles) and mechanical durability (up to 25000 cycles) offer long-term reliability in systems with frequent switching, such as motor starting and shutdown sequences, minimizing service costs and extending replacement cycles. Feature → Business Impact → Application: Front-terminal, bolt-type connections with a 6 N·m tightening torque ensure robust, vibration-resistant mounting and easier retrofits in existing switchgear, enabling rapid upgrades with minimal panel modification. Feature → Business Impact → Application: Compliance and eco-solutions attributes, including UL489, CSA certificates, and CE declarations, reduce regulatory risk and support sustainability goals in industries pursuing responsible procurement and end-of-life considerations for Tmax XT families.

Get a Quick Quote for a ABB 1SDA075073R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA075073R1? Enquire Now

FAQs

The 3P XT2H MCCB is designed for 600 V systems with a 100 A rating and front-terminal connections, compatible with standard busbar sizing (32.5–100 mm²) and bolt terminals, enabling reliable integration into industrial switchgear and control panels.
Installation uses front-terminal bolt connections with a tightening torque of 6 N·m. The device supports busbar connections from 32.5 to 100 mm², simplifying wiring and improving mechanical stability in vibration-prone environments.
This unit carries UL489 certification and CSA certificate 9AKK10103A3906, with a CE Declaration of Conformity for Tmax XT2. These certifications help ensure regulatory compliance across North America and Europe.
Ideal for industrial power distribution and motor protection in machine enclosures, packaging lines, conveyors, and process automation where reliable 3-pole protection, front-terminal access, and easy maintenance are valued.
Key specs include 3P 100 A capacity, 600 V rating, 150 kA (240 V) to 25 kA (600 V) interrupting ratings, and high electrical/mechanical durability. Together with service-friendly installation and regulatory compliance, these factors reduce downtime and maintenance costs.