ABB 1SDA076712R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA076712R1
Manufacturer
ABB
Part number
1SDA076712R1

Quick Summary

ABB 1SDA076712R1 Moulded Case Circuit Breaker is a protective device that interrupts fault currents in low-voltage power distribution. Engineers often face space constraints, reliability concerns, and compliance challenges when upgrading MCCB protection in compact panels. It carries IEC conformity, RoHS/REACH declarations, and CE certification, supporting global installations and responsible sourcing. This 60 A three-pole unit with front-terminal access simplifies panel wiring and reduces maintenance downtime, delivering improved uptime, safer operation, and lower total cost of ownership for panel builders and OEMs. For ready-to-wire protection with minimal enclosure space, this ABB SACE Formula DSA solution fits automatic circuit breaker applications in industrial environments.

Product Information

Extended Description

1SDA076712R1 ABB: C.BREAKER FORMULA A1N 125 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MF R 60-720 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Environmental Information - Formula A1-A2 | Breakers - Packaging disposal information
EAN
8015644827465
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
0.75 kg
Package Level 1 Units
1 piece
Package Level 1 Width
136.5 mm
Package Level 1 Height
124 mm
Package Level 1 Depth / Length
110.5 mm
Package Level 1 Gross Weight
0.8 kg
Package Level 1 EAN
8015644827465
Product Main Type
SACE FORMULA DSA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
3P
Rated Current (In)
Main Circuit 60 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 18 kA | (415 V AC) 7.5 kA | (440 V AC) 6.25 kA | (480 V AC) 4.5 kA | (500 V AC) 2.5 kA | (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 25 kA | (480 V AC) 18 kA | (500 V AC) 10 kA | (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
MF
Release Type
M
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE FORMULA DSA IEC Low voltage molded-case circuit-breakers up to 630A IEC 60947-2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Formula DSA A1
Instructions and Manuals
Installation Instructions Formula A1/III-IV
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Front-terminal, three-pole design with MF release enables quick, safe wiring in compact panels. Business Impact: reduces installation time and wiring errors, improving initial build quality and ongoing maintenance. Application: ideal for low-voltage protection in automation cabinets and motor control centers. Feature: High short-circuit capacity with Ics up to 50 kA at 240 V and Icu up to 100 kA at 240 V. Business Impact: provides robust protection margins for feeders and transformers, lowering nuisance trips and unplanned downtime. Application: suitable for industrial feeders, switchgear, and machine protection schemes. Feature: Mechanical durability of 8500 cycles and electrical durability of 1500 cycles. Business Impact: longer service life reduces replacement costs in high-turnover environments. Application: frequent on/off duty in production lines and power distribution panels. Feature: 60 A nominal current, Ui 690 V insulation, Uo 550 V AC / 250 V DC operation, and 6 kV rated impulse withstand. Business Impact: ensures compatibility with global low-voltage networks and motor loads, enabling one part for multiple markets. Application: suitable for control cabinets, MCCs, and panel feeders in industrial facilities. Feature: Compliance package includes IEC conformity, CE declaration, RoHS/REACH declarations, and CMRT. Business Impact: reduces regulatory risk and supports sustainable procurement, helping meet corporate ESG goals. Application: global deployments and supplier audits in manufacturing, energy, and process industries.

Get a Quick Quote for a ABB 1SDA076712R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA076712R1? Enquire Now

FAQs

Ensure the panel supports front-terminal MCCBs, confirm a 3P mounting footprint, and plan for 60 A feed with secure torque on terminals. Provide room for MF release operation and accessible wiring paths to maintain safe servicing after installation.
Ics is up to 50 kA at 240 V (and 18 kA at 380 V), while Icu is up to 100 kA at 240 V (and 36 kA at 380 V). These ratings establish protection margins for feeders and transformers, reducing the risk of downstream equipment damage during faults.
Yes. With 3P configuration, 60 A rating, 550 V AC / 250 V DC operation, front-terminal connection, and 6 kV impulse withstand, it is well-suited for motor control centers and automated production lines that demand reliable short-circuit protection.
It includes IEC conformity, CE declaration of conformity, RoHS and REACH declarations, and CMRT for conflict minerals reporting, supporting global procurement, audits, and sustainability goals.
Electrical durability is rated at 1500 cycles and mechanical durability at 8500 cycles, providing longer service life and lower lifecycle costs in high-switching installations such as busy production lines.