ABB 1SDA076715R1 Moulded Case Circuit Breaker - IEC DSA
Part Number: 1SDA076715R1
Quick Summary
ABB 1SDA076715R1 Moulded Case Circuit Breaker protects panels by interrupting faults in low-voltage power circuits. For engineers, uptime matters, and dense panel layouts or inaccessible front terminals can slow maintenance and increase risk. It complies with IEC 60947-2 and carries a CE declaration, while RoHS, REACH, CMRT and TSCA declarations support global regulatory compliance. With SACE Formula DSA, a three-pole front-terminal design, and 100 A rated current, it streamlines installation and service while delivering robust protection. This combination helps reduce commissioning time, simplify lifecycle maintenance, and strengthen safety across LV switchgear installations, delivering measurable improvements in reliability and total cost of ownership.
Product Information
Extended Description
1SDA076715R1 ABB: C.BREAKER FORMULA A1N 125 FIXED THREE-POLE WITH FRONT TERMINALS AND MAGNETIC RELEASE MF R 100-1200 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Environmental Information - Formula A1-A2 | Breakers - Packaging disposal information
EAN
8015644827496
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
0.75 kg
Package Level 1 Units
1 piece
Package Level 1 Width
136.5 mm
Package Level 1 Height
124 mm
Package Level 1 Depth / Length
110.5 mm
Package Level 1 Gross Weight
0.8 kg
Package Level 1 EAN
8015644827496
Product Main Type
SACE FORMULA DSA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
3P
Rated Current (In)
Main Circuit 100 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 18 kA | (415 V AC) 7.5 kA | (440 V AC) 6.25 kA | (480 V AC) 4.5 kA | (500 V AC) 2.5 kA | (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 25 kA | (480 V AC) 18 kA | (500 V AC) 10 kA | (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
MF
Release Type
M
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE FORMULA DSA IEC Low voltage molded-case circuit-breakers up to 630A IEC 60947-2 Standard
Declaration of Conformity - CE
EC Declaration of Conformity Formula DSA A1
Instructions and Manuals
Installation Instructions Formula A1/III-IV
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Three-pole front-terminal design → Business Impact: Enables faster wiring, safer terminations, and cleaner panel layouts, reducing installation time and risk during maintenance. Application: Ideal for control panels and compact switchgear where space is limited and serviceability matters. Long-tail keywords: front-terminal MCCB installation, three-pole protection, LV switchgear wiring. Feature: 100 A rated current with MF release → Business Impact: Delivers reliable fault interruption under normal and fault conditions, protecting downstream equipment and reducing downstream failure risk. Application: Main circuit protection in LV distribution centers and transformer-fed panels. Long-tail keywords: 100 A MCCB, MF release, main circuit protection. Feature: High breaking capacities → Business Impact: Supports robust protection across a range of fault currents, minimizing arc energy and equipment damage. Application: Data centers, manufacturing lines, and process control where fault rerouting is critical. Long-tail keywords: Ics 50 kA at 240 V, Icu up to 100 kA. Feature: Wide voltage compatibility → Business Impact: Works with 550 V AC and 250 V DC applications, enabling flexible system integration. Application: Industrial power distribution and automation panels. Long-tail keywords: Ui 690 V, Uimp 6 kV, 550 V AC. Feature: Compliance and durability → Business Impact: Meets IEC and CE standards while offering RoHS/REACH/CMRT/TSCA compliance, reducing regulatory risk and long-term maintenance costs. Application: Global deployments with strict sourcing requirements. Long-tail keywords: RoHS, REACH, CMRT, TSCA compliance. Feature: Compact footprint and weight → Business Impact: 76.2 mm width, 130 mm height, and 0.75 kg weight streamline cabinet space planning and installation. Application: OEM panels and retrofit projects where space conservation matters. Long-tail keywords: product net width 76.2 mm, weight 0.75 kg, compact MCCB.
Get a Quick Quote for a ABB 1SDA076715R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA076715R1?
Enquire Now
FAQs
This MCCB uses a front-terminal connection for straightforward wiring in three-phase panels. Ensure panel cutout tolerances match 76.2 mm width, and secure conductors with appropriate torque. Verify phase sequence, mount in the designated slots, and connect control wiring to the MF release for reliable tripping. Clear labeling and adherence to IEC 60947-2 wiring practices minimize commissioning time and miswiring risk.
The device is rated for 100 A In with a service voltage up to 550 V AC / 250 V DC and Ui of 690 V. It provides a rated short-circuit current (Ics) of up to 50 kA at 240 V AC, and an ultimate short-circuit capacity (Icu) up to 100 kA, across various voltages. These ratings support robust protection for LV distribution and transformer-fed systems.
Yes. The 1SDA076715R1 is specified as a SACE Formula DSA product with a three-pole design and MF release. It is well-suited for transformer protection scenarios in low-voltage distribution, offering front-terminal convenience, precise tripping, and compatibility with standard LV switchgear architectures.
The MCCB adheres to IEC 60947-2, carries a CE declaration, and complies with RoHS and REACH. Additional compliance declarations include CMRT and TSCA where applicable, supporting global supply chains and reducing regulatory risk in multi-region deployments.
With a durable MF magnetic release and mechanically strong 3P design, the unit offers long service life (0.75 kg weight and robust 8500 mechanical cycles). Its front-terminal wiring reduces maintenance time, lowers wiring errors, and improves uptime, contributing to lower lifecycle costs and a favorable ROI in ongoing production environments.