ABB 1SDA080830R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA080830R1
Quick Summary
ABB 1SDA080830R1 Moulded Case Circuit Breaker provides reliable overcurrent protection for low-voltage distribution and transformer feeders. This compact front-terminal XT1 unit is designed to simplify wiring and reduce commissioning time in crowded panels, helping engineers avoid unnecessary field rework. It is built to deliver predictable tripping performance under fault conditions while supporting essential certifications and declarations. With ABB EcoSolutions for end‑of‑life management and compliance programs including RoHS and REACH, the device aligns with broader sustainability goals. For OEMs and panel builders, this translates into easier serviceability, steadier performance, and a lower total cost of ownership across industrial automation projects.
Product Information
Extended Description
1SDA080830R1 ABB: C.BREAKER TMAX XT1S 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 16-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SE3016AFF000XXX
E-Number (Norway)
4379225
EAN
8015644873486
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8015644873486
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMF
Release Type
TM
Setting Range
16 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: 3P XT1 with TMF release provides robust overload and short-circuit protection on low‑voltage feeders. Business Impact: higher fault tolerance and minimized equipment damage, reducing downtime in control panels and distribution boards. Application: motor feeders, transformer protection in automation installations. Feature: Front-terminal connection enables faster wiring and straightforward maintenance. Business Impact: reduced installation time and simplified field service, especially in tight cabinet spaces. Application: panel boards, equipment rooftops, and modular switchgear. Feature: Setting range 16 A with rated current 16 A and rated voltage 690 V enhances selectivity and coordination. Business Impact: precise protection settings that prevent nuisance trips and improve system reliability. Application: distribution circuits and protection zones with mixed loads. Feature: High short-circuit capability with Ics up to 80 kA and Icu up to 85 kA across voltages. Business Impact: guards critical loads against severe faults, lowering the risk of cascading failures. Application: transformer feeders and high‑fault environments. Feature: IEC 60947‑2 compliance, CE declaration, RoHS/REACH, and ABB EcoSolutions support. Business Impact: regulatory peace of mind and sustainability alignment, reducing compliance risk and lifecycle costs. Application: global deployments with strict regulatory requirements. Feature: Compact footprint and light weight (76.2 mm width, 130 mm height, 70 mm depth; 1 kg). Business Impact: easier rack integration and reduced panel footprint, improving installation density. Application: distributed panels and space‑constrained control rooms. Feature: Electrical and mechanical durability specs (Electrical 8000 cycles; Mechanical 25000 cycles). Business Impact: longer service life and lower maintenance frequency. Application: continuous production environments with frequent switching.
Get a Quick Quote for a ABB 1SDA080830R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA080830R1?
Enquire Now
FAQs
The device uses front-terminal wiring for quick, face-access installation. With 3P XT1, it has a width of 76.2 mm, height of 130 mm, and depth of 70 mm, weighing about 1 kg. Follow the XT1 installation instructions to secure mounting and properly tighten terminals for reliable connection and service accessibility.
Rated Current In is 16 A, Rated Voltage Ur 690 V, Rated Insulation Voltage Ui 800 V, and Rated Operational Voltage 690 V AC / 500 V DC. Short-circuit ratings include I_cs up to 80 kA and I_cu up to 85 kA, with a setting range of 16 A and a TMF release, suitable for demanding protection tasks.
Yes. The product carries CE with EC Declaration of Conformity and is RoHS compliant, along with REACH and TSCA declarations where applicable. ABB also provides environmental and packaging guidance, supporting compliant deployment across regions.
Yes. It is part of the SACE Tmax XT family, designed for transformer and distribution protection. Its front-terminal XT1 design, 3P configuration, and TMF release are compatible with Tmax XT protection architectures in new or retrofit transformer and switchgear applications.
Lifecycle features include ABB EcoSolutions and PEPs, with recyclability at 55.9% per EN45555 and available EPDs. Mechanical durability is rated at 25,000 cycles, electrical durability at 8,000 cycles, and packaging/disposal guidance is provided to support sustainable maintenance planning and waste minimization.