ABB 1SDA080832R1 Moulded Case Circuit Breaker - 85 kA Icu

Part Number: 1SDA080832R1
Manufacturer
ABB
Part number
1SDA080832R1

Quick Summary

ABB 1SDA080832R1 Moulded Case Circuit Breaker provides reliable overload and short-circuit protection for industrial power distribution panels. This 3P XT1 device is designed to simplify wiring and maintenance while delivering robust protection in demanding environments. It aligns with IEC60947-2 standards and CE conformity, with RoHS compliance and environmental disclosures available for traceability. Engineers benefit from a compact, front-terminal design that speeds installation and reduces panel depth, while the Tmax XT lineage ensures consistent performance across retrofit projects. By combining a precise setting range with high fault-current withstand, this breaker supports predictable uptime, streamlined maintenance planning, and improved total cost of ownership for critical facilities.

Product Information

Extended Description

1SDA080832R1 ABB: C.BREAKER TMAX XT1S 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 25-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SE3025AFF000XXX
E-Number (Norway)
4379211
EAN
8015644873608
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8015644873608
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMD
Release Type
TM
Setting Range
17.5...25 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal, 3-pole XT1 fixed breaker's design accelerates wiring and replacement, reducing installation time and minimizing field errors, which translates to lower labor costs and quicker energization of critical circuits. The unit’s 690 V rated operational voltage supports typical industrial networks, while its 85 kA Icu capability provides strong short-circuit protection in high fault-current environments, improving safety margins and reducing downstream equipment damage. The 25 A rated current with a setting range of 17.5–25 A offers precise, scalable protection for distribution feeders and transformer protections, enabling tailored protection schemes without oversizing. Mechanical durability of 25,000 cycles and electrical durability of 8,000 cycles extend service life and uptime, delivering cost savings over time. Front wiring compatibility, 76.2 mm width, and fixed front terminals support compact panel layouts and straightforward retrofits in SACE Tmax XT installations. The device is part of the Tmax XT family, ensuring consistent performance with existing ABB protection strategies and EPC/OEM integrations. Compliance with IEC60947-2, RoHS, and CE declarations reinforces regulatory alignment for global projects, while environmental disclosures and EPD data help support sustainability reporting. In practice, customers see reduced commissioning risk, faster maintenance cycles, and a clear path to compliant upgrades in modernization programs.

Get a Quick Quote for a ABB 1SDA080832R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA080832R1? Enquire Now

FAQs

The 1SDA080832R1 is a 3P XT1 molded case breaker with fixed front terminals designed for ABB SACE Tmax XT installation. It fits standard low‑voltage distribution panels that support front wiring, offering a compact footprint (76.2 mm width) and straightforward wiring diagrams. Suitable for new builds and retrofits, it simplifies panel modernization projects by ensuring consistent mounting geometry and wiring pathways.
Key specifications include a rated current of 25 A with a setting range of 17.5–25 A, rated operational voltage of 690 VAC (and 500 V DC), and a rated ultimate short-circuit breaking capacity up to 85 kA. The device is a 3P XT1 with front terminals and a thermal‑magnetic release (TMD), suitable for protecting feeders and transformer/generator circuits in industrial environments.
Yes. The 1SDA080832R1 is designed for power distribution protection in transformer and generator schemes within the Tmax XT family. With 85 kA Icu capability and a 690 V rating, it provides robust short‑circuit protection and can be integrated into protection schemes alongside upstream devices. Front-terminal access plus clear wiring diagrams support reliable integration in complex protection architectures.
The breaker complies with IEC 60947-2, is CE conformant, and RoHS compliant, with DoC documents available. It supports global regulatory requirements and sustainability reporting, including EPD options for Tmax XT XT1, making it suitable for projects with strict environmental and compliance targets.
The 1SDA080832R1 delivers long service life with 25,000 mechanical cycles and 8,000 electrical cycles, reducing maintenance frequency and replacement costs. Its front-terminal design simplifies inspections and wiring checks, minimizing downtime during servicing. Compatibility with Tmax XT systems also aids standardized maintenance procedures across sites, contributing to lower overall ownership costs.