ABB 1SDA080835R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA080835R1
Quick Summary
ABB 1SDA080835R1 is a 3-pole moulded case circuit breaker designed for reliable protection of power distribution in industrial facilities. This model helps engineers avoid nuisance trips and space constraints through front-terminal installation and a precise TMF release for quick, predictable protection. It complies with IEC 60947-2 and CE declarations, while RoHS and REACH declarations plus an Environmental Product Declaration support sustainability and regulatory compliance. Leveraging the SACE Tmax XT family, it combines a compact footprint with scalable current settings and high short-circuit capability. The result is improved system availability, reduced maintenance, and lower lifecycle costs for demanding applications such as transformers, motors, and panel boards.
Product Information
Extended Description
1SDA080835R1 ABB: C.BREAKER TMAX XT1H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 16-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1HE3016AFF000XXX
E-Number (Norway)
4379227
EAN
8015644873639
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8015644873639
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 3p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 52.5 kA | (415 V AC) 37.5 kA | (440 V AC) 32.5 kA | (500 V AC) 25 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 52.5 kA | (500 V DC) 3 Poles in Series 52.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 35 kA | (690 V AC) 10 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMF
Release Type
TM
Setting Range
16 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal construction with fixed three-pole design enables safer, faster wiring and straightforward maintenance. The TMF release provides defined, predictable tripping characteristics, aiding selective protection in complex power-distribution schemes. This combination is ideal for panel-mount assemblies and retrofit projects where space is tight and reliability matters. As part of the ABB SACE Tmax XT family, 1SDA080835R1 delivers consistent protection in demanding environments. Current setting is 16 A with a clear 16 A range, supporting precise coordination with downstream devices and reducing nuisance trips. The result is more stable operation for motors, transformers, and lighting circuits, along with lower energy waste. Installation is straightforward in standard distribution panels using front-terminal connections. Protective capability is robust: Ics up to 80 kA at relevant low-voltage conditions and Icu up to 100 kA depending on voltage, with 3P operation. These ratings enable dependable fault clearing without damaging surrounding equipment, even in high-demand lines. This makes it suitable for feeders, drives, and critical power feeds in manufacturing. Rated insulation voltage is 800 V and rated operational voltage spans 690 V AC / 500 V DC, enabling use across diverse industrial networks. The unit supports front-terminal wiring and a compact footprint, simplifying interior panel layouts and reducing installation time. Compliance and sustainability features include RoHS, REACH, and an environmental product declaration, plus disassembly instructions for end-of-life handling. Recyclability is listed at 55.9% per EN45555, helping meet corporate green targets and supporting recycling programs at end of life. Embedded documentation and WEEE guidance ease regulatory adherence. Physical footprint and weight are compact: 76.2 mm wide, 130 mm high, 70 mm deep, and about 1 kg. Front connection, documented wiring diagram, and standard IEC60947-2 compliance simplify procurement, installation, and future upgrades in control panels and switchboards.
Get a Quick Quote for a ABB 1SDA080835R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA080835R1?
Enquire Now
FAQs
ABB 1SDA080835R1 uses a front-terminal, fixed 3P XT1 configuration designed for straightforward panel installation. It is compatible with the SACE Tmax XT family and standard DIN rail or panel enclosures. When wiring, follow the provided wiring diagram to ensure correct phase ordering and secure connections, and verify adequate clearance for front-entry wiring and terminal torque per commissioning guidelines.
Key specs include 16 A rated current, rated operational voltage of 690 V AC / 500 V DC, rated insulation voltage 800 V, TMF release, 3 poles, and short-circuit ratings up to Ics 80 kA and Icu up to 100 kA depending on voltage. It complies with IEC 60947-2 and supports front-terminal wiring for efficient installation.
Yes. The 3P XT1 device offers high short-circuit capacity and TMF release, enabling selective coordination for motor feeders and transformer protection. Its front-terminal design simplifies cabinet wiring, reducing installation time and improving reliability in motor control centers and transformer-fed panels.
This MCCB is certified to IEC 60947-2, with CE declarations, RoHS and REACH compliance, and an Environmental Product Declaration (EPD). It also provides end-of-life guidance and disassembly instructions to support recycling and regulatory adherence in regulated markets.
The product supports sustainability goals with an EN45555 recyclability rate of 55.9% and provides disassembly instructions to aid end-of-life processing. Packaging disposal information is available, helping facilities meet green targets while maintaining reliable, long-life protection for critical electrical networks.