ABB 1SDA080842R1 Moulded Case Circuit Breaker - Icu 65 kA

Part Number: 1SDA080842R1
Manufacturer
ABB
Part number
1SDA080842R1

Quick Summary

ABB 1SDA080842R1 Moulded Case Circuit Breaker protects industrial power distribution by delivering reliable overcurrent protection for 690 V systems. In busy panel builds, engineers often deal with cramped wiring and difficult access; this device's front-terminal design simplifies wiring and maintenance, reducing install time and risk of errors. It aligns with IEC60947-2 and CE conformity, while RoHS and Environmental Product Declaration (EPD) transparency for the Tmax XT1 family support sustainable asset management. For integrators, the XT1N modular platform enables scalable protection solutions with predictable performance, while TMF release and four-pole construction deliver robust protection for three-phase systems and downstream equipment.

Product Information

Extended Description

1SDA080842R1 ABB: C.BREAKER TMAX XT1N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 16-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1NE4016AFF000XXX
E-Number (Finland)
3640544
E-Number (Norway)
4379252
EAN
8015644873707
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644873707
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA | (230 V AC) 50 kA | (240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 18 kA | (500 V AC) 15 kA | (525 V AC) 11 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA | (230 V AC) 65 kA | (240 V AC) 65 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 36 kA | (500 V AC) 30 kA | (525 V AC) 22 kA | (690 V AC) 6 kA | (250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMF
Release Type
TM
Setting Range
16 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 4P front-terminal design provides reliable three-phase protection with easy front-access wiring, reducing enclosure depth requirements and speeding commissioning in control panels and machine safety cabinets. This translates to shorter installation windows, lower labor costs, and improved wiring reliability in high-density switchgear. Application: suitable for machine protection and distribution boards in manufacturing lines where rapid serviceability matters. Feature → Business Impact → Application: TMF release delivers selective tripping with fast response to short circuits, minimizing nuisance trips and protecting downstream equipment. Application: critical in automated lines and packaging systems where uptime is paramount and fault discrimination is required. Feature → Business Impact → Application: rated 690 V operation and 16 A nominal current across a four-pole chassis supports compact MCCB deployment in mid-range industrial applications with room for future expansion. Application: control panels and transformer feeders that demand robust protection with scalable capacity. Feature → Business Impact → Application: IEC60947-2 compliance and CE/ RoHS declarations provide regulatory assurance and easier supplier audits. Application: projects with strict compliance and sustainability targets. Feature → Business Impact → Application: front-terminal compatibility and compatibility with the SACE Tmax XT family simplify installation in retrofit projects and new builds alike, enabling faster maintenance cycles and standardized component sourcing.

Get a Quick Quote for a ABB 1SDA080842R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA080842R1? Enquire Now

FAQs

ABB 1SDA080842R1 is designed as part of the SACE Tmax XT family and features front-terminal wiring for easy integration into XT panel boards. Its 4P configuration and TMF release support straightforward curtaining of three-phase protection, enabling quick retrofit into existing XT panels without major rework. When matching with XT components, verify impedance and busbar spacing to maintain clearance and fault discrimination.
Key specifications include 16 A rated current (In), rated insulation voltage of 800 V, and rated operational voltage of 690 V AC / 500 V DC. It provides Rated Ultimate Short-Circuit Breaking Capacity Icu up to 65 kA across relevant voltages, and Rated Service Short-Circuit Breaking Capacity Ics up to 50 kA. The device is a 4P unit with TMF release, designed for IEC 60947-2 compliance.
Yes. The product carries a CE Declaration of Conformity for Tmax XT1 and complies with RoHS directives. ABB also provides REACH declarations and CMRT documentation to support supply chain responsibility and compliance audits, making it suitable for regulated manufacturing environments and green procurement programs.
Yes. The device is rated for 690 V AC operation with 800 V rated insulation voltage and front-terminal, four-pole configuration. It supports high-energy protection in medium-voltage control gear, transformer feeders, and distribution panels, ensuring reliable short-circuit interrupting performance in 690 V processes and equipment.
ABB provides End Of Life Disassembling Instructions for Tmax XT XT1, and the EcoSolutions program includes disassembly guidance and packaging disposal information. For maintenance, rely on the TMF release and periodic diagnostics, while planning for refurbishment or replacement in accordance with environmental declarations (EPD) and RoHS compliance to minimize total cost of ownership.