ABB 1SDA080847R1 Moulded Case Breaker - Tmax XT1

Part Number: 1SDA080847R1
Manufacturer
ABB
Part number
1SDA080847R1

Quick Summary

1SDA080847R1 is a moulded case circuit breaker for reliable low-voltage distribution protection. Engineers often face nuisance trips and wiring challenges in compact panels, and this device helps reduce both with a precise thermal-magnetic release and accessible front terminals. Built to IEC 60947-2 and CE compliant, it also carries RoHS and REACH declarations for streamlined regulatory approvals. As part of the SACE Tmax XT family, it supports ABB EcoSolutions initiatives, aiding lifecycle management and end-of-life recycling while delivering dependable protection for industrial power systems. This combination of robust performance and ABB support translates into measurable uptime, safer maintenance, and easier panel integration for end users.

Product Information

Extended Description

1SDA080847R1 ABB: C.BREAKER TMAX XT1S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 25-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SE4025AFF000XXX
E-Number (Norway)
4379240
EAN
8015644873752
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644873752
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMD
Release Type
TM
Setting Range
17.5...25 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: Four-pole XT1 design with front terminals enables reliable three-phase protection and straightforward wiring, reducing panel congestion and installation time in distribution boards. Application: main power feeders in industrial panels benefit from faster energization and easier troubleshooting. Feature → Business Impact → Application: Adjustable Setting Range from 17.5 to 25 A allows precise overcurrent protection tailored to protected circuits, improving selectivity and reducing nuisance trips. Application: machine control panels and feeder circuits in manufacturing lines. Feature → Business Impact → Application: Rated Current 25 A with Rated Insulation Voltage of 690 V and Icu up to 85 kA delivers high fault isolation across typical LV installations, improving safety margins in demanding environments. Application: LV distribution and switchgear assemblies requiring robust short-circuit performance. Feature → Business Impact → Application: Front-terminal connection and 4P configuration simplify wiring and maintenance, enabling quick replacement and clean panel layouts. Application: retrofit projects and new builds in control rooms and MCCs. Feature → Business Impact → Application: Long mechanical and electrical durability (up to 25,000 and 8,000 cycles respectively) translates to lower maintenance costs and reduced downtime over the life of the installation. Application: high-usage control panels in continuous operations. Feature → Business Impact → Application: Compliance with IEC60947-2, CE declarations, RoHS/REACH support, and EPD/CMRT data enable faster procurement and easier regulatory alignment for global deployments. Application: corporate compliance programs and international manufacturing sites.

Get a Quick Quote for a ABB 1SDA080847R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA080847R1? Enquire Now

FAQs

To install the 1SDA080847R1, ensure panel cutouts accommodate four-pole front-terminal devices, secure the breaker firmly, and connect front terminals with properly torqued lugs per manufacturer guidelines. Verify correct seating, ensure the device aligns with the bus and busbar spacing, and perform a no-load functional test before commissioning the protected circuits.
The unit is rated for 25 A nominal current (In), 690 V rated insulation voltage (Ui), and 690 V rated operational voltage. It offers an ultimate short-circuit breaking capacity (Icu) up to 85 kA and a service short-circuit capacity (Ics) up to 80 kA at 230/240 V AC. The device uses a thermal-magnetic release with a setting range of 17.5–25 A.
Yes. The 1SDA080847R1 is part of the SACE Tmax XT family designed for main protection in LV distribution panels. Its four-pole XT1 configuration, front terminals, and robust breaking capacities make it well-suited for manufacturing lines requiring reliable circuit protection, fast fault isolation, and easy integration into existing Tmax XT configurations.
The product carries CE conformity (EC Declaration of Conformity) and IEC60947-2 compliance, along with RoHS and REACH declarations. Additional sustainability data include CMRT for conflict minerals and EPD references for lifecycle assessment. These certifications simplify procurement and regulatory reporting across global facilities.
The device provides up to 25,000 mechanical cycles and 8,000 electrical cycles, supporting high-demand environments. Front-terminal design simplifies wiring changes and maintenance, while modular Tmax XT lineage supports lifecycle planning, easier disassembly for recycling, and alignment with ABB EcoSolutions for long-term operational uptime.