ABB 1SDA080848R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA080848R1
Quick Summary
1SDA080848R1 is a four-pole moulded case circuit breaker designed for motor protection and panel distribution in industrial control systems. Engineers face competing needs for protection, space, and installation costs; this XT1S unit delivers rugged reliability with front-terminal wiring for faster assemblies. The device meets IEC 60947-2 and CE requirements, with RoHS/REACH compliance and EcoSolutions material-use insights that support responsible recycling. In practice, you gain up to 32 A protection with a 22.4–32 A setting range, 690 V operating voltage, and a compact 101.6 mm wide footprint. This combination supports easier maintenance, faster commissioning, and longer equipment lifecycles in motor control centers.
Product Information
Extended Description
1SDA080848R1 ABB: C.BREAKER TMAX XT1S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT1
Environmental Product Declaration - EPD
EPD Tmax XT XT1 (IT) | EPD Tmax XT XT1 (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
SCIP
4eb0570c-46d2-47b1-8df5-fa790aace202 Italy (IT)
Simplified SCIP
652ec5ab-fd9a-4024-b330-7ba1541a08c9 Czech Republic (CZ) | 92eceb14-70fa-42a9-832a-8b4619e0316a Germany (DE) | a412affa-8495-4c8d-b003-ab33fc8004ad Germany (DE) | 2bdde519-46f7-4c0a-ae2f-5d1dd50e0caa Sweden (SE) | c6d69811-f503-4ab2-9818-f61abd5bf58b Germany (DE) | da2f4963-f7d5-48fc-82cf-2345df6accf1 Croatia (HR) | 0f387126-6695-4a37-86de-4928b81ca3c0 Hungary (HU) | a0683edf-6bad-40bf-b967-8edd806459de France (FR) | 1990e202-399c-4c91-8d24-e5be529ecf5c Spain (ES) | 56f43a7c-3a75-4fdb-b485-66f1becddf7c Belgium (BE) | 8d3b156b-dfaa-4d83-9821-e0c116b60d51 Germany (DE) | 77fd9866-8480-4b09-af47-6fdc400983d0 Greece (GR) | 95b31ca1-d5b1-4105-aa61-5874546cb48e France (FR) | badc3669-1177-4909-851c-38c1048a6585 Netherlands (NL) | 6e3bcabe-1333-4cd7-87cf-46ecc1083226 Sweden (SE) | cfd86c8c-de40-4fb5-97fe-c4a04fd7671d Hungary (HU) | d16297e3-bfea-4917-8f7b-96b09bd39583 Poland (PL) | 4e46016c-ce2d-4092-b5cc-69d7411c6db9 Finland (FI) | 8f79bc19-67fd-434d-8b00-45fcef1efee9 Belgium (BE) | abe0c492-dc71-4799-85c7-bd75b65e6262 Estonia (EE) | c98bdc22-05b1-4ae9-a9c7-14e05a9fba75 Denmark (DK) | 425cdf7d-d724-4fa8-bac6-99b6e8262345 Germany (DE) | 98fb3f70-cf46-459e-8089-2a1833f381d3 Portugal (PT) | 309d1fe6-4106-40b5-972f-72307f7d557c Poland (PL) | 8796f107-64dd-4042-bdac-f11df3fe03a9 Bulgaria (BG) | 64150041-9439-416f-a3b9-24c6b46c928b Poland (PL) | c6e54210-d8ae-4dce-9925-c07a32ff60a2 Norway (NO)
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT1SE4032AFF000XXX
E-Number (Norway)
4379241
EAN
8015644873769
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8015644873769
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT1 4p FIXED F
Current Type
AC/DC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Rated Current (In)
32 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA | (230 V AC) 80 kA | (240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMD
Release Type
TM
Setting Range
22.4...32 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Mechanical Drawings
XT1 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT1
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front-terminal design with fixed XT1S wiring simplifies field terminations, reducing wiring time and field termination errors, which speeds up panel assembly and minimizes commissioning delays. The 4P format provides comprehensive three-phase protection in compact spaces, enabling clean, safer control panels and easier spare parts management. Rated current of 32 A with a 22.4–32 A setting range delivers precise protection for motors and transformers while avoiding nuisance trips in dynamic load profiles. The thermomagnetic release TMD delivers fast, reliable protection with an opening time around 30 ms, reducing arc energy and downstream wear. Ics and Icu ratings cover common distribution scenarios, while Ui and Ur values align with modern drives at 690 V and 500 V DC. ECOsolu tions and EN45555 recyclability data support sustainable procurement and end‑of‑life planning. The front-terminal XT1S design, 101.6 mm width, and 690 V operation simplify installation alongside existing SACE Tmax XT XT1 family installations, aiding standardization and spares compatibility. In practice, this translates to lower lifecycle costs, faster project delivery, and improved maintenance planning for motor control centers.
Get a Quick Quote for a ABB 1SDA080848R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA080848R1?
Enquire Now
FAQs
The unit uses fixed front terminals in a 4P format and is designed for XT1 front-access wiring. When planning a panel, ensure adequate space for a 101.6 mm wide device, compatible DIN-rail mounting if applicable, and alignment with XT1 XT2 family devices. Verify wiring clearances and torque specs to achieve reliable terminations and maintain front-access serviceability.
Key ratings include a rated current of 32 A with a 22.4–32 A setting range, rated voltage of 690 V, and insulation voltage of 800 V. It supports AC and DC operation with a 4P configuration and a thermomagnetic release (TMD). Short-circuit ratings vary by voltage, with Ics up to 80 kA at 230–240 V and Icu up to 85 kA at the same voltages, decreasing at higher voltages such as 690 V.
Yes. It complies with IEC 60947-2 and CE (EC Declaration of Conformity). RoHS and REACH declarations apply, and ABB EcoSolutions programs include recyclability data (55.9% per EN45555) and EPDs for Tmax XT XT1. Additional disclosures include CMRT and SCIP entries, aligning with modern regulatory and sustainability expectations.
The XT1S Tmax XT4P is intended for motor protection and distribution in switchgear and control panels. With 32 A nominal current, 690 V operation, and front-terminal access, it suits compact control centers, automated lines, and applications requiring reliable short‑circuit protection and fast fault isolation in industrial environments.
The 1SDA080848R1 combines reliable protection with easy wiring and standardization within the SACE Tmax XT family, reducing installation time and spare parts variety. Its RoHS/REACH compliance and EcoSolutions data support sustainable procurement, while the 1-piece MOQ and defined packaging support streamlined order-to-install workflows and predictable maintenance planning.