ABB 1SDA081064R1 Moulded Case Circuit Breaker - 690 VAC
Part Number: 1SDA081064R1
Quick Summary
ABB 1SDA081064R1 moulded case circuit breaker protects industrial power distribution and transformer feeders. In busy facilities, mis-sizing or delayed tripping can trigger costly downtime and equipment damage. This device is built to IEC standards with CE marking, RoHS and REACH compliance, ensuring regulatory alignment and long-term reliability. Featuring front-terminal mounting and an Ekip E-LSIG release, it simplifies installation, reduces panel depth, and supports quick maintenance cycles. For projects requiring Tmax T5 protection with scalable current ratings, this solution delivers clear business value through safety, uptime, and reduced lifecycle costs.
Product Information
Extended Description
1SDA081064R1 ABB: C.BREAKER TMAX T5S 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP E-LSIG 630 A
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
E-Number (Sweden)
3171012
EAN
8015644876012
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Package Level 1 Width
228 mm
Package Level 1 Height
228 mm
Package Level 1 Depth / Length
286 mm
Package Level 1 Gross Weight
5.1 kg
Package Level 1 EAN
8015644876012
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 30 kA | (690 V AC) 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (380 V AC) 50 kA | (400 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 30 kA | (690 V AC) 25 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip E-LSIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210284M0201 | 1SDC210285M0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
630 A rated current enables robust protection for medium-duty feeder applications, reducing fault-related downtime and extending equipment life. Feature → Business Impact → Application: The fixed front-terminal design streamlines wiring and commissioning, delivering faster panel assembly and easier field service in demanding sites such as manufacturing lines and transformer bays. Feature → Business Impact → Application: E-LSIG solid-state release enhances selective tripping accuracy, minimizing unnecessary outages and improving overall system availability in critical processes. Feature → Business Impact → Application: 690 V AC operation with 8 kV impulse withstand and 1000 V insulation provides resilient performance against surges, supporting safe operation in harsh environments like steel, chemical, and process industries. Feature → Business Impact → Application: 5.1 kg weight and compact dimensions simplify enclosure planning and rack mounting, reducing shipment and handling costs. Feature → Business Impact → Application: Compliance with IEC standards, RoHS/REACH declarations, and CE enable straightforward audits and regulatory peace of mind in global deployments. Feature → Business Impact → Application: 3P configuration with Tmax T5 compatibility ensures scalable protection for mid-to-large distribution panels and transformer feeders, enabling future upgrades without replacing the breaker.
Get a Quick Quote for a ABB 1SDA081064R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA081064R1?
Enquire Now
FAQs
ABB 1SDA081064R1 uses fixed front terminals designed for straightforward wiring in compact enclosures. Its 3P configuration and 630 A rating suit mid to large distribution panels and transformer feeders. When planning install, verify terminal torque specifications and ensure enclosure clearance for 140 mm width and 205 mm height. This design minimizes wiring complexity and accelerates commissioning in new builds or retrofit projects.
Key performance specs include rated current of 630 A, rated operational voltage of 690 V AC, rated insulation voltage of 1000 V, and rated impulse withstand voltage of 8 kV. The 3P configuration, S (short-circuit) performance, and E-LSIG release support fast, selective trips essential for transformer protection and downstream distribution resilience in harsh industrial environments.
Yes. The product carries CE conformity and is RoHS compliant, with DE/DoC documentation for Tmax T5 products. ABB also provides REACH declarations and CMRT for conflict minerals reporting, ensuring regulatory alignment across EU markets and global deployments. This simplifies compliance in multinational projects and reduces risk during audits and procurement reviews.
The 1SDA081064R1 offers measurable value through prolonged service life and reduced downtime. Electrical durability up to 5000 cycles and mechanical durability up to 20000 cycles translate to fewer replacements and maintenance interruptions. Coupled with reliable 690 V protection and E-LSIG reliability, projects realize lower lifecycle costs and improved process availability over time.
To maximize reliability, ensure correct front-terminal connections and secure mounting per torque guidelines, verify insulation integrity, and align with Tmax T5 compatibility. Use appropriate enclosure ratings and environmental protection to maintain release performance. Routine inspection of release mechanism alignment and contact condition, plus adherence to IEC standards, will sustain protection accuracy in demanding industrial applications.