ABB 1SDA081067R1 Moulded Case Circuit Breaker - Ics 200kA

Part Number: 1SDA081067R1
Manufacturer
ABB
Part number
1SDA081067R1

Quick Summary

Moulded Case Circuit Breaker protects industrial power circuits in distribution panels and switchgear. When faults occur, downtime and equipment damage drive high costs; this device delivers fast, reliable tripping with a high fault-current capacity to keep systems safe. It carries CE conformity, RoHS and REACH declarations, CMRT and TSCA declarations to support global compliance in diverse markets. Designed for three-pole operation with a 630 A rating at 690 V AC, it features front-terminal connections for quick installation and streamlined wiring in Tmax T5 panel builds. This combination delivers protection plus ease of procurement and maintenance for engineering and procurement teams.

Product Information

Extended Description

1SDA081067R1 ABB: C.BREAKER TMAX T5V 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP E-LSIG 630 A
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T5 | Breakers - Packaging disposal information
EAN
8015644876043
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Package Level 1 EAN
8015644876043
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle | 60 cycles per hour
Mechanical Durability
20000 cycle | 120 cycles per hour
Number of Poles
3P
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 150 kA | (690 V AC) 80 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA | (230 V AC) 200 kA | (380 V AC) 200 kA | (400 V AC) 200 kA | (415 V AC) 200 kA | (440 V AC) 180 kA | (500 V AC) 150 kA | (690 V AC) 80 kA
Rated Uninterrupted Current (Iu)
630 A
Release
Ekip E-LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers | Front
Data Sheet, Technical Information
1SDC210284M0201 | 1SDC210285M0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T5
Instructions and Manuals
1SDC210033D0202
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature: Three-pole design with 630 A rated current and 690 V AC operation. Business impact: Delivers robust short-circuit protection for power distribution and transformer feeders, supporting Ics up to 200 kA and reducing the risk of cascading faults. Application: Ideal for SACE Tmax T5 installations in industrial panels where high fault tolerance is essential. Feature: Front-terminal connection. Business impact: Simplifies wiring, speeds installation, and minimizes field wiring errors. Application: Efficient in modular switchgear and retrofit projects with limited rear-space access. Feature: Ekip E-LSIG solid-state release. Business impact: Improves tripping reliability and reduces mechanical wear, extending service life in demanding environments. Application: Critical protection in constant or cycling load scenarios.Feature: Comprehensive compliance declarations (CE, RoHS, REACH, CMRT, TSCA). Business impact: Supports global procurement and regulatory audits, reducing compliance risk. Application: Enables deployment across multinational facilities with strict sourcing requirements.Feature: Durability and performance specs (Electrical 5000 cycles @ 60 cph; Mechanical 20000 cycles @ 120 cph). Business impact: Lower maintenance costs and longer replacement intervals, improving total cost of ownership. Application: Frequent switching applications such as transformer protection and panel feeders.Feature: Product packaging and dimensions (140 mm width, 205 mm height, 103.5 mm depth; weight 5.1 kg). Business impact: Predictable space planning and straightforward integration into standard enclosures. Application: Panel assemblies and retrofit projects requiring precise form-factor matching.

Get a Quick Quote for a ABB 1SDA081067R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA081067R1? Enquire Now

FAQs

For installation, ensure adequate clearance for front terminals and access for torqueing lugs to the specified values. The 140 mm width and 103.5 mm depth fit standard enclosures, and the 205 mm height aligns with common MCCB mounting footprints. Verify panel bus connections use the fixed-front terminal style and that conductors are rated for 690 V AC insulation and 630 A continuous operation.
This device is a 3P MCCB rated for 630 A, with rated operational voltage of 690 V AC and rated insulation voltage of 1000 V. It withstands impulses up to 8 kV and provides a service short-circuit breaking capacity up to 200 kA across voltage ranges, with a declared Icu/Ics profile suitable for transformer protection and large distribution feeders.
Yes. The ABB 1SDA081067R1 carries an EC Declaration of Conformity for CE, along with RoHS and REACH declarations. It also references CMRT for conflict minerals reporting and a TSCA declaration, supporting compliance in global supply chains and facilitating audits and supplier qualification processes.
E-LSIG is a solid-state release that provides fast, reliable tripping with minimal mechanical wear. This reduces maintenance cycles and stabilizes protection during frequent switching events, improving system uptime and protecting connected equipment such as transformers and feeders in demanding industrial environments.
ROI improves through longer service life and reduced maintenance due to the 20000 mechanical cycle capability and 5000 electrical cycles at rated conditions. Front-terminal installation speeds wiring and reduces field errors, while compliance declarations simplify audits. The unit’s 690 V capability and high Ics support reliable transformer protection with lower total cost of ownership over time.