ABB 1SDA083033R1 Moulded Case Breaker - UL/CSA

Part Number: 1SDA083033R1
Manufacturer
ABB
Part number
1SDA083033R1

Quick Summary

ABB 1SDA083033R1 Moulded Case Breaker is a high-capacity protective device for power distribution systems. Engineers need reliable trip performance for high-current, 3-pole protection without nuisance tripping. This MCCB carries UL/CSA listings, CE Declaration of Conformity, and RoHS/REACH compliance to support global installations. For procurement and maintenance teams, the compact form factor and front-terminal installation simplify panel design, while the solid-state release enhances reliability and reduces total cost of ownership.

Product Information

Extended Description

1SDA083033R1 ABB: C.BREAKER TMAX T8V 2500 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR332/P MM LSIG R 2500
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Product Environmental Information Tmax T8 | Breakers - Packaging disposal information
Order Code US and Canada
T8VBE3HX00A000XX
EAN
8015644897284
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
427 mm
Product Net Height
382 mm
Product Net Depth / Length
282 mm
Product Net Weight
60 kg
Package Level 1 Width
525 mm
Package Level 1 Height
475 mm
Package Level 1 Depth / Length
695 mm
Package Level 1 Gross Weight
72 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Number of Poles
3P
Rated Current (In)
2500 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
3 kV
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
2500 A
Rated Voltage (Ur)
600 V AC
Release Type
EL
Short-Circuit Performance Level
V
Standards
UL
Sub-type
T8
Interrupting Rating acc. to UL489
(240 V AC) 125 kA | (480 V AC) 125 kA | (600 V AC) 100 kA
Data Sheet, Technical Information
1SDC210028D0201
Declaration of Conformity - CE
EC Declaration of Conformity Tmax T8
Instructions and Manuals
Operating istructions for PR331, PR332 and PR333 | Instruction for installation of T8 EN IEC-UL
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
High current rating and 3P configuration deliver robust protection for heavy loads, reducing the need for multiple devices and simplifying panel layouts in data centers and manufacturing lines. The business impact is lower total installed cost and improved line availability, with clear advantages for power distribution feeders and transformer circuits. Front terminals combined with a solid-state release provide easier wiring, faster, repeatable trips, and reduced maintenance complexity, enabling quicker upgrades and retrofit projects in evolving facilities. The UL/CSA rating and RoHS/REACH compliance give engineering teams confidence in global deployments, while CMRT and TSCA documentation streamline supplier qualification and regulatory audits. Dimensions and weight are optimized for enclosure fit, supporting efficient space planning in compact switchgear rooms and modular substations.

Get a Quick Quote for a ABB 1SDA083033R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA083033R1? Enquire Now

FAQs

To install the ABB 1SDA083033R1 in a 3P MCCB scheme, mount the unit in a panel with front-terminal access, verify the 2500 A rating and 600 V AC ratings, and connect L1, L2, L3 according to the wiring diagram. Use the manufacturer torque specifications and appropriate accessories to ensure secure terminations and compliance with local electrical codes.
The interrupting rating per UL489 is 125 kA at 240 V and 125 kA at 480 V, with 100 kA at 600 V. The Short-Circuit Performance Level is V, and the unit operates at 50/60 Hz, ensuring reliable protection for high-energy feeders and transformer interfaces while meeting UL/CSA requirements.
Yes. The 3P 2500 A Tmax T8 MCCB is designed for heavy-duty power distribution, transformer feeders, and large motor circuits. Front terminals simplify wiring in space-constrained panels, while the solid-state release provides precise, fast tripping to minimize fault energy and protect critical loads during startup or fault events.
The product includes UL/CSA listing, a CE declaration of conformity, and RoHS/REACH compliance. It also provides CMRT and TSCA declarations, enabling smoother audits and supplier qualification for global projects and multinational installations.
The solid-state release reduces mechanical wear, while front-terminal wiring facilitates quick inspections and replacements. These features lower maintenance costs, shorten downtime during maintenance windows, and improve mean time between failures (MTBF) in critical power distribution environments, delivering tangible total cost of ownership improvements over conventional MCCBs.