ABB 1SDA100060R1 Moulded Case Circuit Breaker - CE
Part Number: 1SDA100060R1
Quick Summary
ABB 1SDA100060R1 is a Moulded Case Circuit Breaker designed for reliable power distribution in industrial facilities. This XT2H 160 device delivers robust three-pole protection with front-terminal access to simplify wiring and maintenance. It carries CE conformity, RoHS compliance, and REACH declarations, reflecting regulatory readiness for European installations. By aligning with the SACE Tmax XT family, it supports scalable protection schemes while delivering predictable lifecycle costs, reduced downtime, and safer operation for critical manufacturing and data-center environments.
Product Information
Extended Description
1SDA100060R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 10 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001144
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221001144
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Ekip Dip LSI release enables precise tripping and selective coordination. Benefit: Improves system reliability and reduces nuisance trips, minimizing downtime during fault conditions. Application: Data centers and control panels where accurate protection is essential. Feature: 3P configuration with front terminals for fixed installation. Benefit: Faster wiring, cleaner panel layouts, and easier upgrades without rewiring downstream devices. Application: New builds and retrofit projects in industrial plants. Feature: Rated current 10 A and rated voltage 690 V AC with 160 A Iu. Benefit: Suitable for compact feeders and high-voltage distribution where space and performance balance matters. Application: Machine feeders, MCCs, and transformer protection channels. Feature: Electrical durability/Mechanical durability metrics (120 cycles per hour | 8000 cycle; 240 cycles per hour | 25000 cycle). Benefit: Long-term reliability under both electrical and mechanical cycling reduces maintenance costs. Application: Continuous duty in repetitive start/stop environments. Feature: Environmental and compliance data (EPD, EN45555 recyclability 55.70%, RoHS/REACH). Benefit: Supports sustainable design, total cost of ownership reductions, and regulatory compliance. Application: ESG-focused projects and regulated industries requiring documented declarations.
Get a Quick Quote for a ABB 1SDA100060R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100060R1?
Enquire Now
FAQs
The ABB 1SDA100060R1 is designed as a three-pole XT2 device with fixed front terminals, enabling straightforward retrofits into XT2-based power distribution panels. Its 690 V AC rating and 10 A In make it ideal for compact feeders, while front-terminal access simplifies field wiring and commissioning, reducing install time and potential wiring faults.
For 230/240 V systems, this device provides a rated service short-circuit breaking capacity Ics of up to 100 kA and an ultimate breaking capacity Icu of up to 100 kA, ensuring fast and reliable disconnection. At higher voltages (380–690 V), Ics drops to 70 kA or lower as specified, aligning with IEC/EN standards.
Yes. The unit carries a CE Declaration of Conformity and ABB’s DoC for Tmax XT, along with RoHS compliance and REACH declarations. These certifications support regulatory approval in Europe and help ensure material compliance, traceability, and sustainability throughout the product lifecycle.
Front-terminal design offers clean, accessible wiring and quicker termination in control panels, reducing wiring errors and commissioning time. The fixed 3P configuration provides stable mechanical mounting, while compatibility with the XT family ensures a consistent protection strategy across assemblies and future expansions.
Electrical durability is 120 cycles per hour up to 8000 cycles, and mechanical durability is 240 cycles per hour up to 25000 cycles, indicating strong longevity in typical duty cycles. With low per-pole power loss (0.10 W) and documented environmental declarations (EPD, recyclability), you can expect lower maintenance costs and improved total cost of ownership over time.