ABB 1SDA100062R1 Moulded Case Breaker - Ekip Dip LSI
Part Number: 1SDA100062R1
Quick Summary
ABB 1SDA100062R1 Moulded Case Breaker is a compact protection device for power distribution panels. Engineers often battle space constraints, complex wiring, and the need for reliable fault interruption. It aligns with IEC standards, carries CE conformity, and RoHS compliance for safe, regulator-ready integration. As part of the SACE Tmax XT family, it supports 690 V systems and a 63 A rated current. This translates to reduced spare parts, easier maintenance, and faster panel assembly.
Product Information
Extended Description
1SDA100062R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 63 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001168
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221001168
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 1.70 W
Rated Current (In)
63 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P XT2 design with fixed front terminals and Ekip Dip LSI release. Benefit: simplifies wiring, accelerates installation, and delivers reliable trip signaling in AC applications. Application: ideal for power distribution panels and machine control within manufacturing lines. Feature: Rated 63 A and 690 V AC with up to 100 kA Ics and 8 kV Uimp. Benefit: supports robust fault protection for motors and transformers while tolerating high-energy faults. Application: panel boards and protection blocks in medium-voltage distributions. Feature: Power loss of 1.70 W per pole combined with 8000 electrical and 25000 mechanical cycles. Benefit: reduces heat, extends component life, and lowers maintenance costs. Application: high-cycle environments in continuous production. Feature: RoHS, REACH declarations and CE conformity. Benefit: regulatory compliance simplifies procurement and enables sustainable asset management. Application: regulated industrial sectors requiring traceable compliance. Feature: compact footprint and 1.2 kg weight with front-terminal mounting. Benefit: eases installation in tight spaces and accelerates field replacements. Application: modular panels and compact control cabinets.
Get a Quick Quote for a ABB 1SDA100062R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100062R1?
Enquire Now
FAQs
This device uses front-terminal mounting designed for XT2 3P configurations and is compatible with SACE Tmax XT assemblies. It fits standard low-voltage panels, supports a 690 V AC system, and aligns with IEC standards, CE declarations, and RoHS requirements, making retrofits straightforward and regulator-friendly.
Key specs include a rated current of 63 A, rated voltage of 690 V AC, short-circuit breaking capacity up to 100 kA, and impulse withstand of 8 kV. The unit operates at 50/60 Hz and is designed for AC circuits with three poles, providing reliable protection for motor drives and feeders.
Ekip Dip LSI offers precise trip control with fast opening times (typical 30 ms under rated conditions) and reliable signaling. This enhances selectivity and safety in distribution panels, reduces nuisance trips, and supports quick maintenance and reset in demanding industrial environments.
The product carries IEC standards alignment, CE Declaration of Conformity, RoHS compliance, and REACH declarations. These certifications simplify regulatory audits, support green procurement programs, and reassure buyers in industries with strict compliance requirements such as manufacturing and energy sector installations.
With power loss of 1.70 W per pole, electrical durability of up to 8000 cycles and mechanical durability up to 25000 cycles, the unit reduces heat, downtime, and parts replacement. This translates to lower operating costs, improved line reliability, and a favorable return on investment over asset life in continuous production contexts.