ABB 1SDA100063R1 Moulded Case Circuit Breaker - 690 V
Part Number: 1SDA100063R1
Quick Summary
ABB 1SDA100063R1 Moulded Case Circuit Breaker protects industrial power distribution in switchgear applications. Engineers often face nuisance trips and challenging coordination that drive unplanned downtime, especially during commissioning or changes in load. This device supports CE conformity, RoHS and REACH declarations, and IEC-based safety standards for confident European and global deployments. Built to integrate with the SACE Tmax XT family, it streamlines sourcing, installation, and spare-part compatibility across sites. With 3P protection at 690 V AC and a 100 kA service current capability, you gain reliable isolation, improved uptime, and lower operating costs for growing manufacturing and processing facilities.
Product Information
Extended Description
1SDA100063R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 100 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001175
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221001175
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 4.20 W
Rated Current (In)
100 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P XT2 fixed front terminals with the Ekip Dip LSI release. This design enables rapid, reliable test-and-trip verification during commissioning and routine maintenance, reducing downtime. Front-access terminals also simplify field wiring and inspection tasks in dense switchgear cabinets, supporting safer, faster service in busy production environments. Feature: Rated current of 100 A and rated voltage of 690 V AC with 50/60 Hz operation. This combination supports consistent performance across standard industrial networks and aligns with common upstream protection schemes. The unit's 8 kV impulse withstand and robust insulation ensure safe operation in demanding installations such as motor feeders and transformer feeders. Feature: Short-circuit protection with service breaking capacity up to 100 kA across voltage variants. This capacity enables selective coordination, minimizing downtime while containing fault currents close to the source. The XT2 release and solid-state elements deliver reliable performance in both 220–240 V and higher-voltage distributions. Feature: Energy efficiency and thermal performance with approximately 4.2 W power loss per pole at rated conditions. Lower heat generation supports denser panel layouts and reduces cooling needs in small footprint switchgear. Combined with front-terminal design, this improves installation ease and long-term reliability in continuous-operation environments. Feature: Regulatory and environmental compliance including CE DoC, RoHS status, REACH declaration, and an EPD (9AKK108469A1855). This package reduces sourcing risk and simplifies supplier qualification for European and global projects. Documentation availability supports traceability and lifecycle thinking in sustainability-focused procurement. Feature: Compact physical footprint and weight—90 mm wide, 130 mm high, 82.5 mm deep, and 1.2 kg. The measured dimensions fit common panel cutouts and support straightforward retrofits alongside other XT components. With fixed front terminals and standard wiring diagrams, installation is predictable and fast in new builds or upgrades.
Get a Quick Quote for a ABB 1SDA100063R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100063R1?
Enquire Now
FAQs
ABB 1SDA100063R1 is a three-pole XT2 molded-case circuit breaker designed for fixed front-terminal mounting. It integrates with the SACE Tmax XT family, supports 690 V AC systems, and matches common MCC and panelboard configurations. Its dimensions (90 mm W x 130 mm H x 82.5 mm D) and 1.2 kg weight simplify retrofits and space planning in existing switchgear enclosures.
The device operates at 690 V AC with a rated service short-circuit breaking capacity (Ics) up to 100 kA, depending on voltage level. It also features an 8 kV impulse withstand and RoHS/REACH compliant materials, ensuring robust protection against transients and regulatory alignment across European and global installations.
Yes. The ABB 1SDA100063R1 carries CE conformity and RoHS declarations, along with REACH compliance. It is accompanied by an EPD and related environmental data, supporting regulatory requirements and sustainability goals for European projects and global supply chains.
Common applications include motor feeders, transformer protection, and general power distribution within switchgear and MCCs. The 3P fixed front-terminal design, together with Ekip Dip LSI release, makes it suitable for manufacturing lines, data centers, and critical plant infrastructure where dependable isolation and quick servicing are essential.
Lower energy losses of about 4.2 W per pole reduce heat load in enclosures, supporting denser layouts and reduced cooling costs. Front-terminal design accelerates maintenance, testing, and replacements, while RoHS/REACH and CE DoC streamline supplier qualification and risk management, contributing to lower total cost of ownership over the device lifecycle.