ABB 1SDA100067R1 Moulded Case Circuit Breaker - XT2H 63A 100 kA Ics
Part Number: 1SDA100067R1
Quick Summary
Moulded Case Circuit Breaker protects industrial electrical distribution by quickly interrupting fault currents. ABB's 1SDA100067R1 combines XT2H performance with front-terminal installation to reduce downtime during routine maintenance and emergency trips. Site downtime due to nuisance trips or slow fault isolation is costly; this unit addresses that with precise tripping and fast reset. Certified to IEC standards and CE compliant, with RoHS/REACH declarations, this product aligns with modern sustainability and safety requirements. Leverage XT2H's 63 A rating, 100 kA Ics performance, and 690 V capability to streamline procurement and improve protection strategy. In practice, it supports reliable motor protection, front-terminal installations, and straightforward retrofits for existing panels. This combination of rugged build and global support makes it a sound choice for contract manufacturers and OEM panel builders.
Product Information
Extended Description
1SDA100067R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 63 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001212
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221001212
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 1.70 W
Rated Current (In)
63 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: Front-terminal mounting and compact XT2 form factor simplify installation, reduce panel space, and speed wiring in switchgear and control panels; this translates to faster commissioning and lower labor costs during panel upgrades. Application: Industrial power distribution upgrades and retrofit projects. Feature → Business Impact → Application: Ekip Dip LSIG release enhances operator safety with a reliable, selectable trip unit; enables safer maintenance cycles and improved fault isolation in critical processes. Application: Manufacturing lines with high-resilience protection needs. Feature → Business Impact → Application: 63 A rated current and 100 kA Ics provide robust protection for motors and transformers at 690 V; reduces nuisance trips while staying within panel design limits. Application: Motor drives and transformer protection in process industries. Feature → Business Impact → Application: IEC standard compliance and CE/RoHS/REACH declarations support regulatory alignment and global sourcing; simplifies supplier qualification. Application: Global OEMs and panel builders seeking compliant components. Feature → Business Impact → Application: Front-terminal design and clear wiring diagrams simplify installation, testing, and future maintenance; minimizes errors and service time. Application: Panel builders and service teams working in constrained spaces. Feature → Business Impact → Application: Mechanical durability up to 25,000 cycles and electrical durability up to 8,000 cycles deliver long service life; lowers replacement frequency and total cost of ownership. Application: High-churn industrial environments with frequent protection cycling. Feature → Business Impact → Application: Comprehensive data provision including EPD, recyclability rate, and environmental declarations supports sustainability reporting and responsible procurement. Application: Industries pursuing green compliance and lifecycle assessment.
Get a Quick Quote for a ABB 1SDA100067R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100067R1?
Enquire Now
FAQs
Install the 3P XT2H unit in a compatible panel using its front-terminal wiring arrangement, ensuring alignment with the mounting pattern and busbar connections. Verify the Rated Current (63 A) and Short-Circuit Capacity (Ics up to 100 kA) match the system requirements. Tighten terminals to manufacturer torque specifications, re-check wiring continuity, and test the trip function with a controlled fault simulation before commissioning.
Key specs include a Rated Current (In) of 63 A, Rated Voltage (Ur) of 690 V AC, Rated Impulse Withstand Voltage (Uimp) of 8 kV, and a Short-Circuit Rating (Ics) up to 100 kA. It is a 3P, AC-type release with Ekip Dip LSIG, designed for reliability in industrial power distribution and motor protection scenarios.
Yes. The 1SDA100067R1 is a 3P XT2H molded case circuit breaker with LSIG release designed for motor and transformer protection in 690 V systems. Its high Ics rating supports selective protection and fast shutdown during faults, while the front-terminal design simplifies retrofits in existing drive and switchgear installations.
The product complies with IEC standards and carries a CE Declaration of Conformity. It also provides RoHS and REACH declarations, a recyclable design per EN45555 guidelines, and availability of CMRT documentation upon request. These certifications support regulatory alignment and sustainable procurement for global projects.
Electrical durability is rated up to 8,000 cycles and mechanical durability up to 25,000 cycles, reducing replacement frequency in demanding environments. Front-terminal access speeds installation and maintenance, while RoHS/REACH compliance supports ongoing regulatory compliance. Overall, this translates to lower maintenance costs and higher system availability over the protection device’s life.