ABB 1SDA100074R1 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 1SDA100074R1
Manufacturer
ABB
Part number
1SDA100074R1

Quick Summary

ABB 1SDA100074R1 Moulded Case Circuit Breaker is designed to protect 690 V AC power circuits in industrial control panels and switchgear. The primary function is reliable overload and short-circuit protection for three-phase systems with front-terminal access. This design helps reduce wiring time and minimizes panel depth during installation. Customers often struggle with nuisance trips, limited space, and complex maintenance; the XT2 release and fixed front terminals address those challenges by delivering precise tripping characteristics and straightforward wiring. This product aligns with CE conformity and IEC60947-2 standards, while ABB’s eco-solutions documentation and EPDs reinforce responsible procurement. In practice, it enables safer, more maintainable protection schemes within power distribution, motor control centers, and transformer feeders, supporting predictable performance and lower total cost of ownership.

Product Information

Extended Description

1SDA100074R1 ABB: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LIG R 160 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN) | EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2HE3160CFF000XXX
EAN
8056221001281
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221001281
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.1 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Front terminals and fixed three-pole XT2 release simplify wiring, shorten installation time, and improve safety. This translates into lower labor costs and fewer wiring errors during panel assembly, benefiting control panel builders and electrical contractors in manufacturing facilities. Applications include SACE Tmax XT protection in switchgear and transformer feeders, where reliable isolation is critical. High current rating and robust short-circuit performance deliver fast interruption, reducing arc events and protecting downstream equipment, which translates to fewer unplanned outages and lower maintenance costs. The 690 V AC operating voltage and 8 kV rated impulse withstand support protection of auxiliary drives and high-energy loads in modern plants, while the 3P configuration ensures balanced fault handling across phases. Environmental and compliance credentials, such as CE conformity, RoHS/REACH declarations, and EPD data, help procurement meet sustainability and regulatory requirements. The compact footprint (90 mm width, 130 mm height, 82.5 mm depth) and modest weight (1.12 kg) simplify installation in crowded switchgear and retrofit projects, enabling faster upgrades without compromising safety. Compatibility with ABB Sace Tmax XT family and the XT2 product line supports scalable protection across distributed systems, power distribution units, and control cabinets, delivering consistent performance with reduced lifecycle risk.

Get a Quick Quote for a ABB 1SDA100074R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA100074R1? Enquire Now

FAQs

This unit is designed for three‑pole XT2 configurations with front-terminal connections and is compatible with ABB Sace Tmax XT family panels. It fits standard low‑voltage switchgear and motor control centers, simplifying retrofit projects and panel upgrades while maintaining UL/CE compliance expectations.
Rated current is 160 A with a rated operational voltage of 690 V AC. It offers a rated impulse withstand voltage of 8 kV and a rated service short-circuit breaking capacity of up to 100 kA at lower voltages and 15 kA at 690 V, ensuring reliable fault clearance across typical industrial loads.
Yes. The 3P XT2 design with front terminals is intended for distribution and protection in transformer feeders, switchgear, and large motor circuits. Its 160 A rating and high Ics/Icu capabilities provide robust protection for high-energy loads common in transformer-based power distribution in manufacturing facilities.
The product complies with IEC60947-2 and carries a CE declaration of conformity. ABB also provides EPD documentation for Tmax XT XT2, RoHS/REACH declarations, and recyclability data per EN45555, supporting sustainability and regulatory requirements in procurement processes.
Front-terminal access reduces wiring errors and maintenance time during inspections. Its robust mechanical and electrical durability (high cycle ratings) minimizes wear, while reliable tripping reduces unplanned outages. Together with standardized documentation and easy replacement within the XT ecosystem, this translates to lower total cost of ownership over the product’s lifecycle.