ABB 2TFB100494R1001 Moulded Case Circuit Breaker - Tmax T

Part Number: 1SDA100075R1
Manufacturer
ABB
Part number
1SDA100075R1

Quick Summary

ABB 2TFB100494R1001 moulded case circuit breaker protects low-voltage power distributions in industrial automation panels. By reducing nuisance trips and downtime during fault events, it helps maintain plant uptime and operator safety. Compliance is built-in with RoHS and REACH declarations, CMRT reporting, and packaging guidance that support sustainable sourcing. Designed for the SACE Tmax T generation, it's easy to integrate with ABB panels or third-party switchgear, delivering reliable protection and straightforward service.

Product Information

Extended Description

1SDA100075R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 10 A
Environmental Product Declaration - EPD
9AKK108469A1855 
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001298
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8056221001298
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature – SACE Tmax T platform integration ensures dependable low-voltage protection with predictable trip behavior, reducing unplanned outages and supporting safer machine operation in manufacturing and process environments. Business impact – fewer faults translate to higher line availability and lower maintenance costs, improving overall equipment effectiveness (OEE). Application – suitable for machine builders and panel shops implementing compact, scalable protection in power distribution schemes. Paragraph two – The current range for this family spans 250 A up to 1600 A, enabling seamless coordination with downstream protection devices and large motor loads, while maintaining short-circuit resilience and fast isolation. Paragraph three – With a compact footprint (76 mm W x 130 mm H x 70 mm D) and a weight of 1.22 kg, installation is straightforward in standard enclosures and integrated panel layouts, reducing panel depth requirements and simplifying spare parts management. Paragraph four – Regulatory readiness is built in through RoHS and REACH declarations, CMRT reporting, and WEEE packaging guidance, helping procurement teams meet sustainability, traceability, and supplier qualification goals. Paragraph five – Compatibility and lifecycle advantages include ABB’s standard mounting footprint and easy accessory integration with SACE Tmax T components, minimizing engineering changes during upgrades and ensuring dependable long-term service. Paragraph six – In practice, selecting this MCCB supports predictable maintenance planning, safer commissioning, and clearer documentation for audits and compliance programs.

Get a Quick Quote for a ABB 1SDA100075R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA100075R1? Enquire Now

FAQs

Follow the standard ABB mounting footprint and use approved SACE Tmax T accessories for panel compatibility. Verify terminal torque per the datasheet, ensure clean busbar connections, and provide safe isolation during commissioning. Design the panel layout to accommodate the 76 mm width, 130 mm height, and 70 mm depth for reliable fit and service access.
This MCCB belongs to the SACE Tmax T family, with ratings ranging from 250 A up to 1600 A. It offers robust short-circuit protection and facilitates stepwise coordination with downstream protection devices, enabling precise protection for feeders, motors, and distribution circuits while simplifying selectivity analysis.
Yes. The SACE Tmax T platform is designed for motor and circuit protection in industrial settings. When applied with appropriate protection settings and accessories, it provides safe switching, controlled motor starting, and reliable fault isolation, which minimizes wear on drive trains and reduces unscheduled downtime.
The product includes RoHS Declaration, REACH Declaration, and CMRT (Conflict Minerals Reporting Template) information, along with WEEE packaging guidance. These declarations support compliant sourcing, traceability, and sustainable procurement in regulated industries and global supply chains.
The MCCB design emphasizes reliability and long service life, with straightforward maintenance procedures and readily available spare parts. Its compatibility with standard ABB panels and accessories reduces downtime during upgrades or replacements, contributing to lower lifecycle costs and improved asset reliability.