ABB 1SDA100076R1 Moulded Case Circuit Breaker - CE
Part Number: 1SDA100076R1
Quick Summary
ABB 1SDA100076R1 Moulded Case Circuit Breaker provides 4-pole AC protection for low-voltage distribution. This compact device helps simplify panel wiring and reduce downtime during installations. CE conformity under EC Declaration of Conformity, RoHS and REACH compliance, and a design that supports closing resource loops per EN45555 underline its sustainability credentials. The XT2 family’s front-terminal architecture accelerates commissioning, while seamless compatibility with ABB SACE Tmax XT systems ensures predictable performance and easier maintenance for industrial, data center, and machinery enclosures.
Product Information
Extended Description
1SDA100076R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 25 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001304
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8056221001304
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 0.80 W
Rated Current (In)
25 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature Ekip Dip LSI release enables precise fault clearance with predictable tripping curves, delivering improved safety and reduced downstream faults. Benefit Faster fault isolation minimizes downtime and protects downstream equipment in distribution panels. Application Suitable for machine builders and electrical installers integrating with the SACE Tmax XT family in low-voltage networks. Feature Four-pole fixed front-terminal design simplifies wiring and terminal access, reducing installation time and error. Benefit Streamlined commissioning and safer, more reliable enclosure assemblies in new builds or upgrades. Application Ideal for compact, hard-wired protection in control panels and power distribution blocks. Feature Rated current of 25 A with rated voltage up to 690 V AC and IEC-compliant performance ensures robust protection across common industrial applications. Benefit Supports standardization across equipment racks and transformer feeders while maintaining thermal performance with a per-pole power loss of 0.80 W. Application Works well in mixed-load environments where stability and consistent breaking capacity are critical. Feature High short-circuit capability (Ics up to 100 kA depending on voltage) and 8 kV impulse withstand provide strong grid protection. Benefit Reduces the risk of catastrophic faults in critical assets and enables safer startup/shutdown sequences. Application Suitable for transformer protection and process lines in warehouses, factories, and automation cells. Feature RoHS and REACH compliance with EN45555 recyclability rating of 55.70% plus an EPD reference (9AKK108469A1855). Benefit Supports regulatory compliance and sustainability programs while enabling end-of-life resource recovery. Application For industries with strict material restrictions and environmental reporting, such as automotive, packaging, and process manufacturing.
Get a Quick Quote for a ABB 1SDA100076R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100076R1?
Enquire Now
FAQs
Plan for a 4-pole arrangement with fixed front-terminal access to simplify wiring in compact panels. The device uses XT2 front terminals and weighs 1.6 kg with dimensions 120 mm wide, 130 mm high and 82.5 mm deep. Refer to Installation Instructions XT2 and the Wiring Diagram covering XT1 through XT4 to ensure correct mounting, clearance, and safe terminal torque during commissioning.
Rated current is 25 A, and rated voltage is 690 V AC. It offers a rated impulse withstand voltage of 8 kV and supports a high short-circuit capacity (Ics) dependent on voltage, with 50/60 Hz operation. The breaker provides 4P configuration, opening time around 30 ms, and a per-pole power loss of 0.80 W, ensuring efficient thermal performance in protection schemes.
Yes. The product is part of the SACE Tmax XT family, designed for integration with XT2 front-terminal configurations. Its 4P fixed front-terminal design and Ekip Dip LSI release simplify wiring, testing, and maintenance within Tmax XT installations used in distribution panels, transformers, and machinery protection schemes.
The device carries CE conformity via the EC Declaration of Conformity and complies with RoHS and REACH specifications. It also aligns with EN45555 recyclability requirements (55.70%) and has an associated environmental product declaration (EPD) 9AKK108469A1855. CMRT documentation is available on demand to support responsible sourcing initiatives.
With a 4P fixed-front design and robust Ekip Dip LSI release, installation and maintenance are streamlined, reducing panel downtime. Mechanical durability reaches up to 25,000 cycles and electrical durability around 8,000 cycles per hour, supporting long service life in continuous operation environments. The combination of compact footprint, reliable tripping, and CE/RoHS/REACH compliance helps minimize risk and lifecycle costs.