ABB 1SDA100080R1 Moulded Case Circuit Breaker - 690 V AC
Part Number: 1SDA100080R1
Quick Summary
ABB 1SDA100080R1 is a moulded‑case circuit breaker for power distribution in industrial control panels. Many engineers grapple with compact spaces, dependable short‑circuit protection, and seamless integration with existing switchgear. This device meets CE conformity, IEC standards, and RoHS compliance to support regulatory adherence and uptime. As part of the ABB SACE Tmax XT family, it enhances installation efficiency and lifecycle cost management for panel builders and OEMs, delivering reliable protection with scalable performance.
Product Information
Extended Description
1SDA100080R1 ABB: C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 10 A
Environmental Product Declaration - EPD
9AKK108469A1855
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221001342
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8056221001342
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
XT2
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 4P fixed front-terminal XT2 design simplifies wiring and reduces installation errors. Benefit: Faster panel assembly and better signal integrity, especially in dense control cabinets and switchgear racks. Application: Power distribution boards in manufacturing lines and machine control panels benefit from reliable, space‑efficient protection. Feature: Ekip Dip LSIG solid‑state release provides quick, predictable tripping characteristics. Benefit: Enhanced short‑circuit protection with clear fault indication, improving uptime and maintenance planning. Application: Critical loads and motor circuits in automation cells requiring precise coordination. Feature: 10 A rated current with high Ics/Icu across multiple voltages. Benefit: Flexible protection for small to medium loads while safeguarding downstream equipment from faults. Application: Panel feeders and protection modules in low‑to‑mid voltage distributions (up to 690 V AC). Feature: 690 V AC rated operational voltage and 1000 V insulation voltage. Benefit: Expanded compatibility for modern industrial power networks with robust insulating margins. Application: Industrial feeders, transformers, and control circuits in mixed‑voltage environments. Feature: Mechanical durability (25,000 cycles) and electrical durability (8,000 cycles) with low power loss (0.10 W per pole). Benefit: Reduced maintenance downtime and lower running costs over the product lifecycle. Application: Frequent switching tasks in automated lines, where endurance matters. Feature: Front terminal wiring diagrams and XT2 mechanical drawings available. Benefit: Easier installation, faster commissioning, and fewer miswires. Application: OEM panel assembly and retrofit projects requiring clear installation guidance and reliable mounting. Feature: Recyclability considerations and RoHS/REACH compliance. Benefit: Regulatory alignment and sustainable end‑of‑life management for panel manufacturers. Application: Global projects with strict environmental requirements and waste reduction goals.
Get a Quick Quote for a ABB 1SDA100080R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA100080R1?
Enquire Now
FAQs
The device is a fixed 4P XT2 with front terminals, designed for straightforward installation in standard panel layouts. It aligns with XT2/MCCB wiring diagrams and comes with mechanical drawings for XT2 3P-4P fixed front-terminal configurations, enabling fast retrofit or new panel builds without specialized tooling.
Rated current is 10 A, with Rated Operational Voltage 690 V AC and Rated Insulation Voltage 1000 V AC. Short-circuit capability (Ics) reaches up to 100 kA at 230/240 V, 70 kA at 380–440 V, and 15 kA at 690 V, while Icu values follow the same voltage tiers. Release is Ekip Dip LSIG, ensuring reliable tripping behavior.
Yes. It belongs to the SACE Tmax XT family, with a four‑pole configuration ideal for transformer and panel protection in industrial automation. Its 4P fixed front terminals, LSIG release, and compatibility with XT series diagrams support motor protection, control panel distribution, and high‑reliability applications in manufacturing lines.
The product complies with CE conformity and IEC standards, with RoHS and REACH declarations applicable to ABB Sace circuit breakers. It also aligns with environmental considerations such as EN45555 recyclability and provides DoC‑CE documentation for conformity assessment in European markets.
Electrical durability is rated at 8,000 cycles and mechanical durability at 25,000 cycles, with a low power loss of 0.10 W per pole. These metrics translate to predictable maintenance intervals, reduced downtime, and lower total cost of ownership in busy production environments.