ABB 1SDA101950R1 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 1SDA101950R1
Quick Summary
ABB 1SDA101950R1 Moulded Case Circuit Breaker is a protective device for low‑voltage power distribution in industrial installations. It helps prevent damage from overcurrent events, enabling safer panels and reduced downtime. This XT2 LIG 3P model complies with key standards while delivering reliable switching performance in demanding environments. For design teams facing space constraints, front-terminal mounting and compact form factor streamline wiring and serviceability. By leveraging ABB EcoSolutions and recyclability data, it also supports sustainability goals and lifecycle cost control. The combination of robust electrical characteristics and ABB Sace lineage delivers predictable protection, faster commissioning, and lower total cost of ownership in panel and distribution applications.
Product Information
Extended Description
1SDA101950R1 ABB: C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LIG R 10 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
Order Code US and Canada
XT2LE3010CFF000XXX
EAN
8056221019941
Minimum Order Quantity
1 piece
Customs Tariff Number
85389099
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
120 mm
Package Level 1 Height
160 mm
Package Level 1 Depth / Length
190 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8056221019941
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Feature → Business Impact → Application: The 3P XT2 front-terminal design enables straightforward wiring and faster installation in control panels, reducing commissioning time and error-prone wiring. This improves project timelines in power distribution scenarios and minimizes field labor costs. Feature → Application → Benefit: Rated current of 10 A with a 690 V AC/500 V DC operating range supports compact protection for auxiliary circuits and small feeders within industrial plants, enabling safe motor and transformer protection without oversizing devices. Feature → Benefit → Application: Ics up to 150 kA and Icu ratings ensure robust short-circuit performance for transformer and generation protection in medium‑voltage distribution schemes, increasing system reliability and reducing the risk of cascading faults. Feature → Application → Objection: Release type Ekip Dip LIG with front terminals simplifies maintenance and field testing; with 30 ms opening times (SOR/UVR depending on variant), it minimizes fault impact and supports fast fault isolation. Feature → Benefit → Application: 1000 V rated insulation and 690 V AC operating voltage meet common European and global electrical codes, facilitating global procurement and reducing engineering complexity for multi-site projects. Feature → Application → Objection: Mechanical durability (up to 25000 cycles) and electrical durability (up to 8000 cycles at 120 cycles/hour) address lifecycle expectations in high‑duty panels, providing predictable maintenance schedules and lowering replacement costs. Feature → Benefit → Application: Environmental and recyclability data (EPD, EN45555 compliant, 55.7% recyclability) support sustainability reporting and end‑of‑life planning for modern green facilities, aligning with corporate ESG targets and waste reduction initiatives.
Get a Quick Quote for a ABB 1SDA101950R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA101950R1?
Enquire Now
FAQs
This 3P XT2 unit features front terminals and compact dimensions (90 mm width, 130 mm height, 82.5 mm depth) designed for space‑constrained panels. It supports straightforward front wiring, reducing enclosure changes and simplifying panel layouts while maintaining safe clearance and easy accessibility for testing and maintenance.
Key specs include a rated current of 10 A, rated insulation voltage of 1000 V, rated operational voltage of 690 V AC / 500 V DC, Ics up to 150 kA, and Icu up to 150 kA (depending on voltage). It uses AC release (EL) with Ekip Dip LIG, and a 3P configuration, suitable for transformer, motor, and feeder protection in low‑voltage systems.
Yes. The device is covered by the CE Declaration of Conformity for Tmax XT series, with RoHS and REACH declarations for ABB Sace circuit breakers. It also includes TSCA documentation where applicable and aligns with EN45555 recyclability guidance for end‑of‑life planning.
Front terminals facilitate quick rewiring and field testing, reducing downtime during servicing. Mechanical durability is rated up to 25,000 cycles and electrical durability up to 8,000 cycles at typical duty, enabling predictable maintenance windows. The device is compatible with SACE Tmax XT family components, supporting future expansions or replacements without rewiring.
The product carries an Environmental Product Declaration (EPD) for Tmax XT XT2 ELT and a Design for Closing Resource Loops rating per EN45555, with a recyclability rate of 55.7%. Packaging disposal guidance is provided, aiding responsible end‑of‑life management and supporting corporate sustainability reporting.