ABB 1SDA102078R1 Moulded Case Circuit Breaker - UL/CSA XT2
Part Number: 1SDA102078R1
Quick Summary
ABB 1SDA102078R1 Moulded Case Circuit Breaker protects power distribution panels in industrial installations. Sourcing a UL/CSA-rated MCCB that fits front-terminal wiring and XT2 dimensions for complex panel builds can be challenging. This device carries UL and CSA conformity, plus CE Declaration of Conformity and RoHS/REACH declarations, aligning with global safety and sustainability expectations. By combining robustness with easy wiring and a compact footprint, it helps maintain uptime while reducing wiring errors. In practice, engineers value the Ekip Dip LSI release for precise sensing and the XT2 family’s compatibility with common protection schemes.
Product Information
Extended Description
1SDA102078R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSI R 100 A
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8056221021210
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.22 kg
Package Level 1 EAN
8056221021210
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 3p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 4.20 W
Rated Current (In)
100 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL
Sub-type
XT2
Interrupting Rating acc. to UL489
(240 V AC) 150 A | (480 V AC) 65 A | (600 V AC) 25 A
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature 1: Front-terminal, fixed 3-pole design. Business Impact: Simplifies wiring and reduces installation time, improving panel assembly accuracy. Application: Ideal for compact distribution panels in industrial plants where layout is tight and wiring must stay organized. Long-tail keywords: XT2 front-terminal MCCB, 3-pole switchgear, compact protective device. Feature 2: Ekip Dip LSI solid-state release. Business Impact: Delivers reliable, precise tripping with fast response to faults, lowering downtime risk. Application: Suitable for motor control centers and power distribution where precise protection is critical. Long-tail keywords: Ekip Dip LSI release, latch/spring trip technology, UL/CSA protection unit. Feature 3: Rated current and voltage ensemble. Business Impact: 100 A capacity with 690 V AC, enabling safe handling of sizable loads while meeting common industrial specs. Application: Panel boards for machines, conveyors, and process equipment. Long-tail keywords: MCCB 100 A, 690 V AC protection, high-power distribution. Feature 4: Power loss and efficiency. Business Impact: 4.20 W loss per pole minimizes heat in the enclosure, supporting energy efficiency and thermal management. Application: Dense switchgear where heat rise is a concern. Long-tail keywords: low power loss MCCB, energy-efficient protection, thermal management in panels. Feature 5: Compliance and sustainability. Business Impact: EPD, RoHS, and REACH declarations support responsible procurement and compliance reporting. Application: Projects with ESG requirements and recyclability targets. Long-tail keywords: RoHS compliance, REACH declaration, recyclability EN45555. Feature 6: Mechanical and electrical durability. Business Impact: UL/CSA conformity with 50/60 Hz operation and robust mechanical ratings reduces maintenance cycles and extends service life. Application: Continuous operation in demanding environments. Long-tail keywords: UL489 standard, 3P MCCB durability, industrial protection.
Get a Quick Quote for a ABB 1SDA102078R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA102078R1?
Enquire Now
FAQs
This MCCB is a fixed, three-pole unit with front terminals designed for straightforward wiring in panel boards. It aligns with the XT2 family footprint, enabling quick drop-in replacement or upgrade in legacy SACE Tmax XT installations. For best results, follow the XT2 3p fixed front terminals wiring diagram and install in compliant enclosures.
Rated current is 100 A with a rated voltage of 690 V AC, and a rated insulation voltage of 1000 V AC. It operates at 50/60 Hz and has a release type Ekip Dip LSI. UL489 interrupting ratings are 150 A at 240 V, 65 A at 480 V, and 25 A at 600 V, supporting reliable protection across typical industrial loads.
Yes. It is part of the SACE Tmax XT XT2 family, designed as a fixed front-terminal MCCB with Ekip Dip LSI release. This ensures compatibility with XT series protection schemes, standardized trip behavior, and common wiring practices across ABB’s Tmax XT lineup.
The device carries UL/CSA conformity, and a CE Declaration of Conformity for Tmax XT2. It also supports RoHS and REACH declarations, plus an Environmental Product Declaration (EPD) and recyclability information (55.70% per EN45555) for sustainable procurement and compliance reporting.
With 4.20 W power loss per pole, front-terminal wiring for fast wiring and reduced installer risk, and a robust Ekip Dip LSI release for precise tripping, the MCCB supports lower maintenance costs and higher line reliability. UL/CSA certification further reduces compliance risk in regulated industries.