ABB 1SDA102137R1 Moulded Case Circuit Breaker - UL/CSA

Part Number: 1SDA102137R1
Manufacturer
ABB
Part number
1SDA102137R1

Quick Summary

ABB 1SDA102137R1 Moulded Case Circuit Breaker protects power distribution panels and motor circuits in industrial settings. This device addresses wiring complexity, space constraints, and uptime requirements common in critical electrical installs. It carries UL/CSA approvals, CE conformity, and RoHS/REACH compliance to simplify global procurement and traceability. Designed for Tmax XT families, the 4-pole, front-terminal configuration with Ekip Dip LSIG release delivers reliable protection with straightforward installation. By combining compact form with durable mechanical life and predictable electrical performance, it supports faster commissioning, easier field servicing, and reduced total cost of ownership for panel builders and OEMs.

Product Information

Extended Description

1SDA102137R1 ABB: C.BREAKER TMAX XT2H 125 UL/CSA FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LSIG R 10 A
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (IT)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.70 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
EAN
8015644026486
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Height
208 mm
Package Level 1 Depth / Length
145 mm
Package Level 1 Gross Weight
1.6 kg
Package Level 1 EAN
8015644026486
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
XT2 4p FIXED F
Current Type
AC
Electrical Durability
120 cycles per hour | 8000 cycle
Mechanical Durability
240 cycles per hour | 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 30 ms | CB with UVR 30 ms
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL
Sub-type
XT2
Interrupting Rating acc. to UL489
(240 V AC) 150 A | (480 V AC) 65 A | (600 V AC) 25 A
ATEX Certificate
No certification needed
Data Sheet, Technical Information
SACE Tmax XT UL/CSA Low voltage molded case circuit-breakers UL489 and CSA CS22.2 Standards Catalog | SACE Tmax XT UL/CSA TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers for UL489 and CSA CS22.2 Standards
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
UL Certificate
1SDL000163R0112
VDE Certificate
No certification needed
Mechanical Drawings
XT2 3p-4p fixed front terminals
Wiring Diagram
Circuit diagram for XT1, XT2, XT3 and XT4
Instructions and Manuals
Installation instructions XT2 UL | XT2-XT4 Trip Unit Ekip Dip LSI-LSIG
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC001023 - Shunt release (for power circuit breaker)
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: Front-terminal 4-pole design simplifies wiring, reduces installation time and wiring errors, enabling quicker panel assembly and easier maintenance in control cabinets for heavy machinery. Feature → Application: Ekip Dip LSIG release provides reliable tripping with LSIG functionality, supporting coordinated protection strategies in automation lines and distributed motor networks, improving uptime and safety. Feature → Benefit: Rated current of 10 A and rated operating voltage of 690 V AC align with common industrial feeders, enabling compact protection in compact switchgear while meeting UL489/CSA CS22.2 standards. Feature → Outcome: Power loss per pole is only 0.10 W, delivering energy efficiency in continuous operation and lower heat within crowded panel spaces. Feature → Compliance: RoHS and REACH declarations, plus an EPD and EN45555 recyclability data, simplify regulatory reporting and support sustainable design. Feature → Durability: Electrical durability up to 8000 cycles and mechanical durability up to 25000 cycles increase service intervals and total cost of ownership, reducing maintenance costs over the product life. Feature → Compatibility: Front-terminal mounting and 120 x 130 x 82.5 mm footprint fit standard 4P XT2 slots, improving replacement fit and minimizing cabinet redesign requirements.

Get a Quick Quote for a ABB 1SDA102137R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA102137R1? Enquire Now

FAQs

For ABB 1SDA102137R1, use the fixed front-terminal 4P configuration to simplify wiring in control panels. Refer to the XT2 mechanical drawings and wiring diagram for XT1–XT4 configurations. The unit weighs 1.6 kg and has a footprint of 120 mm by 130 mm by 82.5 mm, facilitating compact panel integration and straightforward field wiring.
The breaker is rated 10 A (In), with rated insulation voltage 1000 V AC and rated operational voltage 690 V AC. It supports 50/60 Hz inputs, features AC current type, and provides a 4P configuration with an Ekip Dip LSIG release. Power loss is 0.10 W per pole, enabling efficient operation in dense panels.
Yes. The product is UL489 and CSA CS22.2 compliant, with a UL certificate (1SDL000163R0112) and a CE Declaration of Conformity for Tmax XT2, ensuring broad regulatory acceptance across North America and Europe.
ABB 1SDA102137R1 supports RoHS and REACH declarations, along with an Environmental Product Declaration (EPD) and a recyclability rate per EN45555. These disclosures help with sustainability reporting and compliant end-of-life management for global deployments.
Ideal for power distribution and motor protection in control cabinets and machine panels, the 1SDA102137R1 combines front-terminal wiring, LSIG release, and UL/CSA compliance to deliver reliable overload and short-circuit protection in 690 V AC systems with compact installation footprints.