Quick Summary

ABB 1SDA116229R1 is a moulded case circuit breaker used to protect power distribution in industrial automation. It helps prevent nuisance trips and unplanned downtime caused by overloads and short circuits. The device carries IEC standards with RoHS and REACH declarations, ensuring regulatory compliance across global facilities. This MCCB is designed for P1 configurations with front terminals, delivering reliable protection and easy installation to reduce lifecycle costs. With 3P operation and a 25 A rating, it seamlessly fits P1 power distribution in industrial plants, process lines, and packaging facilities. Its 50/60 Hz compatibility and 500 V AC / 250 V DC operating range support diverse machine architectures.

Product Information

Extended Description

1SDA116229R1 ABB: C.BREAKER FORMULA DSP P1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 25-450 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221083379
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8056221083379
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P1
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
2.00 W
Rated Current (In)
25 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
17.5…25 A
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
P1
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The three-pole, front-terminal design reduces wiring time during installation, speeding commissioning and lowering labor costs while enhancing reliability in control panels and switchgear assemblies. This comes with a robust thermomagnetic release (TMD) that improves protection against short circuits, reducing equipment damage and unplanned downtime in critical process lines. Rated at 25 A and 500 V AC / 250 V DC, it supports responsive protection for mixed voltage systems across general manufacturing floors and packaging lines. The setting range of 17.5–25 A enables precise coordination with upstream protection, minimizing nuisance trips and preserving production continuity. Mechanical durability of 20000 cycles provides long service life in high-cycle environments, lowering replacement frequency and total cost of ownership. RoHS and REACH compliance, IEC standards, and CMRT/TSCA declarations strengthen regulatory alignment, supporting audits and global deployments.

Get a Quick Quote for a ABB 1SDA116229R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116229R1? Enquire Now

FAQs

The ABB 1SDA116229R1 uses a front-terminal connection design ideal for compact control panels and switchgear. It supports standard 3P MCCB mounting in P1 power distribution configurations, enabling straightforward wiring, quick inspection, and reliable bolt-in installation in enclosures sized for moulded case breakers.
Key specs include three poles, 25 A rated current, 500 V AC and 250 V DC rated operational voltage, 8 kV rated impulse withstand, 450 A instantaneous short-circuit current setting, and 2 W power loss. The device supports 50/60 Hz operation, front-terminal terminals, and a setting range of 17.5–25 A for precise coordination with upstream protection.
Yes. The part is explicitly listed as suitable for P1 configurations and power distribution tasks. Its front-terminal design simplifies wiring, while its 3P arrangement provides robust protection for three-phase systems common in manufacturing and packaging lines, aligning with typical plant protection schemes and OEM installations.
The product includes IEC standards certification along with RoHS and REACH declarations. Additional compliance information includes CMRT (Conflict Minerals Reporting Template) and TSCA declarations, plus WEEE categorization, supporting global audits and region-specific regulatory requirements.
With a mechanical durability of up to 20000 cycles and a modest 2 W power loss, the MCCB delivers low operational wear and reduced operating costs. Front-terminal wiring speeds installation, while IEC, RoHS, REACH, and TSCA compliance reduces compliance risk. The device’s reliability translates into fewer maintenance calls and downtime, delivering a favorable total cost of ownership in busy production environments.