ABB 1SDA116232R1 Moulded Case Circuit Breaker - 40 kA Ics

Part Number: 1SDA116232R1
Manufacturer
ABB
Part number
1SDA116232R1

Quick Summary

ABB 1SDA116232R1 is a moulded case circuit breaker that protects power distribution networks in industrial control panels. Engineers often struggle with crowded switchgear, frequent nuisance tripping, and protecting multiple feeds with minimal downtime. This device is RoHS and REACH compliant, with CMRT and TSCA declarations, and it aligns to IEC standards for reliable performance. By combining robust short-circuit protection with front-terminal installation, it reduces wiring time and supports compliant, efficient panel design. For procurement teams, this model offers predictable lead times, easy stocking, and compatibility with P1 architecture. It also supports safe, scalable protection in evolving industrial environments. The result is a dependable, maintenance-friendly solution that helps minimize downtime and optimize energy use.

Product Information

Extended Description

1SDA116232R1 ABB: C.BREAKER FORMULA DSP P1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 50-500 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221083409
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8056221083409
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P1
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
3.70 W
Rated Current (In)
50 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
35…50 A
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
P1
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The unit employs a 3-pole configuration with a front-terminal connection and a thermal-magnetic release (TMD), delivering precise overcurrent protection and fast fault clearance. This translates to reduced downtime and extended equipment life in distribution panels and control cabinets. Application: Suitable for P1 distribution layouts where rapid response and compact wiring are critical. Feature → Business Impact → Application: Rated current of 50 A combined with a setting range of 35–50 A enables precise coordination with downstream protection while accommodating load fluctuations. Application: Ideal for machinery feeds and motor-control circuits in manufacturing lines, with improved selectivity and energy efficiency. Feature → Business Impact → Application: High short-circuit withstand (Ics up to 40 kA at 240 V AC) provides robust protection against fault currents, reducing collateral damage and maintenance costs. Application: Critical in high-demand electrical rooms and panel boards requiring dependable protection. Feature → Business Impact → Application: Front-terminal, compact footprint (76.2 mm width, 130 mm height, 70 mm depth) simplifies installation in tight spaces and streamlines panel design. Application: Retrofit projects and new builds where space and wiring simplicity matter. Feature → Business Impact → Application: RoHS, REACH, CMRT, and TSCA declarations ensure regulatory compliance across regions, minimizing supply-chain risk. Application: Global deployments with strict material and reporting requirements. Feature → Business Impact → Application: Power loss rated at 3.70 W supports energy-conscious designs, contributing to reduced heat generation and improved cooling budgets. Application: Continuous operation environments where thermal management is a consideration. Insight: The product aligns with IEC standards and SACE Formula DSP family characteristics, making it a familiar, integration-friendly choice for engineers upgrading existing assemblies.

Get a Quick Quote for a ABB 1SDA116232R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116232R1? Enquire Now

FAQs

Front-terminal design simplifies wiring in crowded panels, but ensure torque specifications and terminal clearance meet the installation manual. Verify correct orientation to maintain reliable tripping and ease future maintenance.
Rated current is 50 A with a setting range of 35–50 A, rated voltage 500 V AC / 250 V DC, Ui 750 V, Ics up to 40 kA (at 240 V AC), and 3P configuration with a 60 Hz operation window compatible with IEC standards.
Yes. The device carries RoHS and REACH declarations, along with CMRT and TSCA documentation, supporting regulatory compliance across multiple regions.
It is designed for power distribution and motor protection in control panels and switchboards, particularly where space is limited and reliable protection is essential, such as packaging, food & beverage, and general manufacturing environments.
It adheres to IEC standards, provides C-type short-circuit performance, and features a 3-pole, front-terminal configuration with a thermal-magnetic release (TMD) for dependable, industry-grade protection in distribution systems.