ABB 1SDA116239R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA116239R1
Quick Summary
Moulded Case Circuit Breaker ABB 1SDA116239R1 provides reliable overload and short-circuit protection for power distribution panels. Engineers often struggle to balance precise tripping, compact installation space, and straightforward front-terminal wiring. This device addresses those needs with a front-access terminal design, a thermomagnetic release, and a robust 4-pole configuration. It is manufactured to IEC standards and is RoHS, REACH, and TSCA compliant, with CMRT tracking for responsible sourcing. Being part of the SACE FORMULA DSP family, it supports easy coordination with other protection devices and helps reduce spare parts and maintenance costs. The result is safer, more efficient panel assembly and quicker commissioning for P1 applications.
Product Information
Extended Description
1SDA116239R1 ABB: C.BREAKER FORMULA DSP P1C 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 20-450 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221083478
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.3 kg
Package Level 1 Units
1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.4 kg
Package Level 1 EAN
8056221083478
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P1
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
1.80 W
Rated Current (In)
20 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
14…20 A
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
P1
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole moulded-case design with front terminals and a thermomagnetic release (TMD) provides precise, reliable protection for 20 A circuits. Business impact: reduces nuisance trips and simplifies wiring during installation and maintenance. Application: ideal for power distribution panels and control cabinets in industrial facilities. Feature: Setting range of 14–20 A with a fixed rated current of 20 A and compatibility with 50/60 Hz systems. Business impact: enables selective coordination with upstream protection and predictable response under fault conditions. Application: panel feeders and downstream protection in P1 distribution networks. Feature: High short-circuit rating with Ics up to 40 kA (varies by voltage) and Icu up to 40 kA. Business impact: enhances fault tolerance and safety in high-demand motor and line applications. Application: factory automation, machine processes, and heavy-load feeders. Feature: Low power loss at 1.80 W and mechanical durability rated at 20,000 cycles. Business impact: lowers energy consumption and reduces maintenance downtime over the product lifecycle. Application: continuous operation in demanding manufacturing environments. Feature: Comprehensive compliance and packaging information including RoHS, REACH, CMRT, TSCA, and EAN packaging. Business impact: simplifies regulatory compliance, traceability, and global procurement. Application: multinational plants and regulated industries requiring rigorous sourcing data.
Get a Quick Quote for a ABB 1SDA116239R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA116239R1?
Enquire Now
FAQs
For ABB 1SDA116239R1, use the front-terminal design to simplify wiring and reduce panel depth. The 4P arrangement fits compact enclosures, and torque specifications should follow the ABB installation instructions to ensure secure terminations. With a width of 101.6 mm and a depth of 70 mm, plan the panel layout to accommodate adjacent devices while allowing easy access for maintenance.
This device provides 20 A rated current at 500 V AC / 250 V DC, with a 14–20 A setting range and a 450 A instantaneous short-circuit setting. It offers Ics up to 40 kA (varies by voltage) and Icu up to 40 kA, along with Ui of 750 V and Uimp of 8 kV, suitable for demanding distribution and protection tasks in P1 applications.
Yes. The product is categorized as a Moulded Case Circuit Breaker in the SACE FORMULA DSP family, with a 4P configuration and front-terminal access tailored for P1 power distribution. Its tripping characteristics, voltage ratings, and high short-circuit capacities support safe, reliable panel protection in industrial environments.
The device adheres to IEC standards and maintains RoHS and REACH declarations. TSCA compliance is documented, and CMRT provides supply-chain transparency. These certifications help mitigate regulatory risk and support sustainable procurement practices across global manufacturing operations.
With a mechanical durability rating of 20,000 cycles and a power loss of 1.80 W, this MCCB is designed for long life with minimal energy waste. Plan routine visual inspections, verify torque at terminations, and coordinate with upstream protections to minimize nuisance trips. Its front-terminal design also simplifies preventive maintenance and replacement in busy panels.