ABB 1SDA116276R1 Moulded Case Circuit Breaker - 80kA

Part Number: 1SDA116276R1
Manufacturer
ABB
Part number
1SDA116276R1

Quick Summary

The ABB 1SDA116276R1 Moulded Case Circuit Breaker protects power distribution in industrial facilities. Engineers often balance fast fault isolation with reliable operation, easy installation, and regulatory compliance within crowded panels. This model carries IEC standards alignment, RoHS and REACH declarations, and CMRT reporting to streamline global supply chains. With a compact 3P front-connection design and a TMF release, it fits tight spaces while delivering dependable fault clearance and lower lifecycle costs. Designed for P1 power distribution, it integrates seamlessly with ABB SACE DSP products, offering protection, coordination, and serviceability with minimal panel disruption.

Product Information

Extended Description

1SDA116276R1 ABB: P1S 160 TMF 20-450 3p F F
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221083843
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8056221083843
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P1
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
1.80 W
Rated Current (In)
20 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 25 kA | (500 V AC) 4 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMF
Release Type
TM
Setting Range
20 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P1
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: High short-circuit protection with Ics up to 80 kA at 240 V AC. Business Impact: Enables safe, rapid isolation during faults, reducing downtime and equipment damage. Application: Ideal for motor feeders and distribution panels in industrial environments. Long-tail keyword integration includes 80 kA Ics protection, P1 distribution protection, and TMF-based trip characteristics. Feature: Front-terminal 3P connection design. Business Impact: Simplifies wiring during panel assembly, minimizes wiring errors, and speeds commissioning. Application: Suitable for tight control cabinets and compact switchgear layouts where accessibility is limited. Feature: Rated currents and voltage ranges (In 20 A; Ur 500 V AC / 250 V DC). Business Impact: Enables safe operation across mixed AC/DC systems while preserving coordination with upstream protection. Application: Common in general purpose feeders and mixed-voltage motor circuits. Feature: Mechanical durability and low power loss. Business Impact: Extends service life and reduces heat-related losses in continuous operation, improving energy efficiency. Application: Critical for high-cycle assemblies and service-intensive environments. Feature: Compliance and environmental data (IEC, RoHS, REACH, CMRT, TSCA, WEEE). Business Impact: Streamlines procurement, reduces compliance risk, and supports sustainability goals across global supply chains. Application: Helpful for regulated industries and multinational deployments. Feature: Physical footprint and weight. Business Impact: 76.2 mm width, 130 mm height, 70 mm depth with a 1 kg net weight enables plug-and-play replacement and minimal panel real estate usage. Application: Panel upgrades and retrofits where space is at a premium. The content reflects real-world usage in P1 distribution scenarios, aligning with long-tail keywords such as 3P MCB front-terminal, 20 A MCB with 80 kA, SACE FORMULA DSP, and TMF release for ABB industrial protection.

Get a Quick Quote for a ABB 1SDA116276R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116276R1? Enquire Now

FAQs

Yes. The device uses a front-terminal connection and is designed for 3-pole configurations in P1 power distribution. Its compact footprint (76.2 mm wide, 130 mm high, 70 mm deep) supports straightforward panel integration and minimizes wiring complexity during installation.
It provides an instantaneous setting up to 450 A with a service short-circuit capacity Ics up to 80 kA (at 240 V AC) and supports rated operational voltages of 500 V AC / 250 V DC. This makes it suitable for mixed-voltage motor feeders and control circuits.
The breaker aligns with IEC standards and carries RoHS and REACH declarations, CMRT reporting for conflict minerals, TSCA compliance, and WEEE categorization, ensuring regulatory compliance across global markets and sustainable practices.
The 3P front-terminal design simplifies wiring and serviceability, reducing commissioning time. Its compact size, 1 kg net weight, and direct compatibility with P1 distribution schemes help minimize panel space requirements and enable easier retrofits and routine maintenance.
Low power loss (1.80 W) and high mechanical durability (up to 20,000 cycles) reduce energy consumption and maintenance cycles. Coupled with IEC, RoHS/REACH compliance and CMRT reporting, it lowers regulatory risk and downtime, delivering measurable ROI in high-demand industrial environments.