ABB 1SDA116309R1 Moulded Case Circuit Breaker - IEC 8 kV
Part Number: 1SDA116309R1
Quick Summary
ABB 1SDA116309R1 is a 3-pole moulded case circuit breaker for industrial power distribution. Wiring access, panel space, and reliable fault protection are common challenges engineers face, which this unit addresses with front terminals and a precise thermomagnetic release. It carries IEC certification and declarations for RoHS, REACH, and TSCA, plus CMRT support for responsible sourcing. Its 160 A rating, adjustable 112–160 A setting, and front-connection design translate into faster commissioning and safer, more maintainable protection across control panels. Designed for distribution boards and motor control centers, it supports both AC and DC applications up to 500 V AC and 250 V DC. This combination helps reduce risk and total cost of ownership.
Product Information
Extended Description
1SDA116309R1 ABB: C.BREAKER FORMULA DSP P1H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084178
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
76.2 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1 kg
Package Level 1 Units
1 piece
Package Level 1 Width
128 mm
Package Level 1 Height
135 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Gross Weight
1.1 kg
Package Level 1 EAN
8056221084178
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P1
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
15.00 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1600 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 32.5 kA | (500 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 10 kA | (250 V DC) 2 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
112…160 A
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
P1
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Front terminals with a TM release provide direct wiring and fast, clear manual operation. This reduces installation time in panel builds and minimizes wiring errors, improving commissioning schedules. It is ideal for space-constrained panels and MCCs where front-access is preferred. Adjustable setting range 112–160 A supports precise overcurrent protection, improving selective coordination, reducing nuisance trips, and extending motor life by matching protection to load. The 3P design, rated 500 V AC / 250 V DC, simplifies dual-voltage applications and standardizes protection across mixed loads in industrial plants. Short-circuit performance options include Ics up to 80 kA at 240 V AC and 50 kA at 380–415 V AC, with Icu up to 100 kA at 240 V AC and 70 kA at 380–415 V AC, delivering robust fault withstand for critical feeders. Compliance and sustainability across RoHS, REACH, CMRT, and TSCA reduce regulatory risk and support responsible sourcing, easing global procurement for energy and process industries.
Get a Quick Quote for a ABB 1SDA116309R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA116309R1?
Enquire Now
FAQs
Install the unit using the front-terminal connections to simplify wiring and reduce panel depth. Follow the manufacturer’s installation instructions, secure the device and wiring with the recommended hardware, and confirm correct alignment with a trained technician. Ensure compatible busbars and terminal torque specifications per the datasheet to maintain fault protection reliability.
The MCCB is rated for 160 A with an adjustable setting range of 112–160 A, supports 50/60 Hz operation, and provides protection up to 500 V AC and 250 V DC. It has an impulse withstand voltage of 8 kV, front-terminal connections, and a release type of TMD for precise overcurrent protection with 3 poles.
Yes. The device is designed for P1 protection with adjustable settings, 3P configuration, and front-connection terminals, making it suitable for distribution boards and motor control centers where reliable protection and easy maintenance are required.
It carries IEC standards, RoHS and REACH declarations, TSCA compliance, CMRT for responsible sourcing, and WEEE packaging information, supporting global regulatory requirements and environmentally responsible procurement.
Mechanical durability is rated for up to 20,000 cycles, with a 240 cycles-per-hour capability, enabling predictable maintenance intervals. Its modular, front-access design reduces downtime during inspections, and the RoHS/REACH/CMRT compliance simplifies supplier management and minimizes regulatory risk, delivering lower total cost of ownership in continuous operation environments.