ABB 1SDA116347R1 Moulded Case Breaker - SACE DSP
Part Number: 1SDA116347R1
Quick Summary
ABB 1SDA116347R1 is a 3P moulded case breaker used for P2 power distribution in industrial cabinets. Engineers face the challenge of delivering reliable overload and short-circuit protection without complicating installation or maintenance. This device carries IEC conformity along with RoHS and REACH declarations and supports CMRT (Conflict Minerals Reporting) and TSCA, helping manufacturers meet global regulatory requirements. With a rated current of 125 A, a setting range of 87.5–125 A, and a rated operational voltage of 500 VAC / 250 VDC, it delivers scalable protection across diverse plant sections. The combination of compact form factor, front-terminal wiring, and robust performance translates into lower installation time, reduced spare parts, and safer, more reliable power distribution for industrial environments.
Product Information
Extended Description
1SDA116347R1 ABB: P2S 250 TMD 125-1250 3p F F
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084550
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.6 kg
Package Level 1 Units
1 piece
Package Level 1 Width
155 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
1.7 kg
Package Level 1 EAN
8056221084550
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P2
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
6.60 W
Rated Current (In)
125 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 20 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 6 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
87.5…125 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P2
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
The 3P moulded case breaker design protects three-phase loads in common switchgear cabinets, enabling coordinated shutoff across all lines and preventing exposed-arcing during faults. This configuration reduces fault cascades, speeds up recovery, and is ideal for P2 power distribution in control panels and industrial automation racks. The 125 A rated current with an adjustable setting range of 87.5–125 A and an instantaneous I_i of 1250 A provides precise protection, improving motor protection coordination and minimizing nuisance trips in high-load lines. Front terminal connections simplify wiring, accelerate installation, and ease future maintenance or retrofits in existing equipment. Rated voltage of 500 V AC / 250 V DC with Ui of 750 V supports mixed-voltage automation architectures, enhancing universal applicability across plant networks. High short-circuit performance (I_cs up to 50 kA at 240 V AC and 36 kA at higher voltages) combined with I_cu up to 50 kA ensures robust fault handling. The device’s mechanical durability of up to 20000 cycles and a compact footprint reduce replacement intervals and maintenance costs. A measured power loss of 6.60 W minimizes heat load, lowering cooling requirements in enclosed cabinets. Compliance with RoHS, REACH, CMRT, and TSCA, plus WEEE considerations, simplifies cross-border sourcing and regulatory reporting. This MCCB is well-suited for P2 distribution in automation cells, machine lines, and multi-vendor control panels, delivering reliable protection with predictable lifecycle costs.
Get a Quick Quote for a ABB 1SDA116347R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA116347R1?
Enquire Now