Quick Summary

ABB 1SDA116353R1 is a high-capacity moulded case circuit breaker designed for reliable power distribution in industrial panels. Engineers often struggle to balance protection performance with installation footprint and lifecycle costs. This model aligns with IEC standards and carries RoHS and REACH declarations, plus CMRT and TSCA compliance, ensuring regulatory peace of mind. With a 4-pole arrangement, 200 A rated current, and a scalable 140–200 A setting range, it accommodates evolving protection schemes in modern plants. Its compact footprint, front-terminal connection, and documented technical data streamline installation while delivering predictable maintenance and energy efficiency in P2 distribution applications.

Product Information

Extended Description

1SDA116353R1 ABB: P2S 250 TMD 200-2000 4p F F InN=50%
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084611
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
2 kg
Package Level 1 Units
1 piece
Package Level 1 Width
155 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
2.1 kg
Package Level 1 EAN
8056221084611
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P2
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
13.20 W
Rated Current (In)
200 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
2000 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 20 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 6 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
140…200 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P2
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 4-pole protection with 200 A rating enables precise coordination in P2 power distribution, reducing nuisance trips and downtime. Business Impact: improves plant uptime and lowers maintenance costs by avoiding over- or under-protection. Application: ideal for feeders and motor circuits in industrial panels. Feature: Adjustable setting range of 140–200 A provides selective coordination and adaptability to load growth. Business Impact: minimizes unnecessary outages while preserving safety margins; Application: scalable protection for evolving line-ups and renewables interface. Feature: High fault-current capability with Ics up to 50 kA (240 V) and 36 kA (380–440 V) and Icu up to 50 kA ensures robust protection for critical feeders. Business Impact: reduces risk of equipment damage and downtime during short circuits; Application: heavy-duty distribution and motor starter banks. Feature: Low power loss of 13.2 W improves thermal performance and cooling efficiency. Business Impact: lowers energy consumption and cooling load; Application: continuous operation in compact switchboards. Feature: 20000 mechanical durability cycles at 240 cycles/hour extends service life and reduces replacement frequency. Business Impact: lowers total cost of ownership; Application: high-cycle control panels in manufacturing lines. Feature: Compliance suite (IEC standards, RoHS, REACH, CMRT, TSCA) provides regulatory alignment and easier procurement. Business Impact: speeds time-to-spec and reduces compliance risk; Application: global manufacturing environments requiring strict material declarations. Feature: Front-terminal connection and 4P form factor enable straightforward installation and neat wiring. Business Impact: reduces install time and error potential; Application: panel builders and retrofit projects in P2 protection schemes. Industry context: as part of the SACE FORMULA DSP family, the ABB 1SDA116353R1 supports modular protection architectures, aiding engineers in delivering reliable power distribution with predictable maintenance and lifecycle costs.

Get a Quick Quote for a ABB 1SDA116353R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116353R1? Enquire Now