ABB 1SDA116367R1 Moulded Case Breaker - 4P 125A 8kV

Part Number: 1SDA116367R1
Manufacturer
ABB
Part number
1SDA116367R1

Quick Summary

ABB 1SDA116367R1 is a moulded case breaker for P2 power distribution in industrial panels. Engineers often face space constraints and demand reliable, easy-to-install protection with clear compliance data. It complies with IEC standards and carries RoHS/REACH declarations, plus CMRT and TSCA reporting to support global supply chains. By selecting this ABB MCCB, you gain a precise 87.5–125 A setting range, front-terminal installation, and robust short-circuit protection, delivering measurable value in panel density, maintenance planning, and regulatory compliance.

Product Information

Extended Description

1SDA116367R1 ABB: P2H 250 TMD 125-1250 4p F F InN=100%
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084758
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
2 kg
Package Level 1 Units
1 piece
Package Level 1 Width
155 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
2.1 kg
Package Level 1 EAN
8056221084758
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P2
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
6.60 W
Rated Current (In)
125 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 60 kA | (500 V AC) 8 kA | (250 V DC) 2 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
87.5…125 A
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
P2
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 4-pole configuration provides coordinated protection for multi-phase loads, enabling tighter control of fault conditions and improved panel density in power distribution systems. This translates to reduced wiring complexity and faster panel assembly in manufacturing lines, with the flexibility of an adjustable setting range (87.5–125 A) to match varying motor and process loads in P2 applications. Implementing this MCCB supports efficient commissioning and reliable protection for control cabinets across machine tools and process industries. Long-tail keywords such as P2 power distribution MCCB and adjustable protective devices are part of the value proposition here, addressing modern panel-building workflows. Feature → Business Impact → Application: Front-terminal connection simplifies installation, shortening commissioning time and reducing field wiring errors. This is particularly advantageous in retrofit projects where existing cabinets are designed for front-access components, and it supports faster maintenance cycles in high-availability environments. Feature → Business Impact → Application: High fault-current ratings (Ics up to 50 kA at 240 V; Icu up to 70 kA at 380–415 V) offer strong fault resistance for critical equipment like CNCs and conveyors, improving overall plant safety margins and minimizing unplanned downtime. Feature → Business Impact → Application: Release characteristics (TMD, TM) deliver selective tripping and predictable fault clearance, which improves coordination with upstream protection and minimizes unnecessary cascades in complex distribution networks. Feature → Business Impact → Application: Material compliance and environmental declarations (RoHS, REACH, CMRT, TSCA) help procurement meet regulatory requirements and support global supply-chain governance, easing audits and customer certifications while maintaining a compact footprint and consistent performance. The combination of compact dimensions (140 mm width, 150 mm height, 70 mm depth) and a 2 kg weight enables easier enclosure planning and transport, especially in retrofit projects where space is at a premium.

Get a Quick Quote for a ABB 1SDA116367R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116367R1? Enquire Now