ABB 1SDA116369R1 Moulded Case Circuit Breaker - IEC
Part Number: 1SDA116369R1
Quick Summary
ABB 1SDA116369R1 is a moulded case circuit breaker designed to protect power distribution systems in industrial plants. This device helps engineers avoid nuisance tripping, minimize panel downtime, and simplify fault isolation in high-density electrical installations. It carries IEC standards compliance and RoHS/REACH declarations, plus CMRT for responsible sourcing, ensuring traceable, compliant performance across projects. With adjustable protection (Setting Range 140–200 A) and front-terminal installation, it supports straightforward wiring and retrofit, while its low power loss promotes cooler panels and reduced cooling costs. In short, this MCCB delivers reliable protection, lifecycle efficiency, and clear compliance for modern power distribution.
Product Information
Extended Description
1SDA116369R1 ABB: P2H 250 TMD 200-2000 4p F F InN=100%
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084772
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
2 kg
Package Level 1 Units
1 piece
Package Level 1 Width
155 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
2.1 kg
Package Level 1 EAN
8056221084772
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P2
Version
F
Current Type
AC/DC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
13.20 W
Rated Current (In)
200 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
2000 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 30 kA | (500 V AC) 3 kA | (250 V DC) 2 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 60 kA | (500 V AC) 8 kA | (250 V DC) 2 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMD
Release Type
TM
Setting Range
140…200 A
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
P2
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole design with rated current of 200 A and a 140–200 A setting range. Business Impact: Enables precise protection and selective tripping in 4P configurations, reducing unnecessary outages and enabling safer motor control and distribution. Application: Suitable for compact industrial panels and switchgear where space optimization and accurate fault isolation matter. Feature: TM release type with P2H 250 TMD compatibility and adjustable trip characteristics. Business Impact: Provides adjustable protection tailored to specific loads and motor starting conditions, improving process reliability and reducing unplanned downtime. Application: Ideal for P2H/Power Distribution schemas in manufacturing lines and packaging facilities. Feature: High short-circuit capability (Ics up to 50 kA at 240 V AC and Icu up to ~70 kA depending on voltage). Business Impact: Ensures safe interruption and fault containment for heavy load systems, supporting compliance with stringent electrical codes. Application: Critical in large panels and feeders delivering high starting currents. Feature: RoHS, REACH declarations and CMRT. Business Impact: Demonstrates regulatory compliance and responsible sourcing, reducing supplier risk and enabling easier customer audits. Application: Essential for projects requiring traceable material compliance and sustainability reporting. Feature: Front-terminal connection and 4P configuration with power loss of 13.20 W. Business Impact: Simplifies installation, reduces wiring complexity, and minimizes thermal load in enclosures. Application: Preferred for retrofit and new installations in existing panel layouts. Feature: Rated voltage of 500 V AC / 250 V DC and IEC standard conformance. Business Impact: Broad compatibility with standard industrial controls and DC bus applications, enabling cross-application use. Application: Power distribution in mixed AC/DC environments and modern automation systems.
Get a Quick Quote for a ABB 1SDA116369R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA116369R1?
Enquire Now