ABB 1SDA116384R1 Moulded Case Circuit Breaker - IEC Ics

Part Number: 1SDA116384R1
Manufacturer
ABB
Part number
1SDA116384R1

Quick Summary

ABB 1SDA116384R1 is a four-pole moulded case circuit breaker designed for P3 protection in industrial power distribution applications. Engineers often confront nuisance trips and limited protection coordination; this device provides a wide setting range and a reliable release to minimize downtime. It carries IEC standards along with REACH, RoHS, CMRT and TSCA declarations, ensuring regulatory compliance across regions. Its compact footprint (186 mm wide, 205 mm high, 103 mm deep) with front-terminal connections supports easy installation in existing switchgear while delivering high uninterrupted current ratings and robust durability. This makes it a dependable choice for modern power systems requiring precise protection and streamlined maintenance within the SACE FORMULA DSP family.

Product Information

Extended Description

1SDA116384R1 ABB: P3S 400 TMA 400-4000 4p F F InN=50%In
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221084925
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103 mm
Product Net Weight
5.8 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
5.8 kg
Package Level 1 EAN
8056221084925
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P3
Version
F
Current Type
AC/DC
Mechanical Durability
15000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
24.10 W
Rated Current (In)
400 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
2000…4000 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 18 kA | (250 V DC) 2 Poles in Series 35 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 25 kA | (250 V DC) 2 Poles in Series 35 kA
Rated Uninterrupted Current (Iu)
400 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMA
Release Type
TM
Setting Range
280…400 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P3
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
1SDH002124A1001
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: Rated current of 400 A with a setting range of 280–400 A enables selective protection and reduced nuisance trips in 4P distribution panels, improving uptime and fault isolation in industrial facilities. Application: motor feeders and process lines where precise current limiting is critical. Feature → Business Impact → Application: Short-circuit performance up to 80 kA (at 240 V) and 50 kA (380–440 V) with a rated insulation voltage of 750 V and a 500 V AC / 250 V DC rating provide robust protection for high-energy systems, reducing equipment damage and downtime in critical processes. Application: central distribution boards and industrial control panels requiring high fault withstand. Feature → Business Impact → Application: Mechanical durability of 15,000 cycles and 24.10 W power loss support long service life and energy efficiency, lowering maintenance costs and energy waste in high-switching environments. Application: frequent switching in power distribution and safety interlock applications. Feature → Business Impact → Application: RoHS, REACH, CMRT and TSCA declarations ensure full regulatory compliance and traceability across global supply chains, mitigating compliance risk for multinational projects. Application: global installations with strict material and reporting requirements. Feature → Business Impact → Application: Front-terminal connection and 186x205x103 mm footprint simplify installation and retrofit projects, saving mounting space and reducing installation time in retrofit and new builds. Application: compact switchgear upgrades and panel redesigns where space is at a premium. Feature → Business Impact → Application: Part of the SACE FORMULA DSP family and suitable for P3 protection, aligning with established ABB protection schemes and enabling straightforward integration with existing protection relays and assemblies. Application: modular protection strategy in switchboards and power distribution centers.

Get a Quick Quote for a ABB 1SDA116384R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116384R1? Enquire Now

FAQs

Yes. This ABB moulded case circuit breaker is designed for front-terminal connection and 4P configurations used in typical P3 protection schemes. It integrates with the SACE FORMULA DSP family and supports common switchgear footprints, enabling straightforward retrofits and panel upgrades.
The device is rated for 400 A nominal current with a 280–400 A setting range, 500 V AC / 250 V DC, and short-circuit ratings up to 80 kA at 240 V and 50 kA at higher voltages. It also features a 750 V insulation rating and a 4P configuration, suitable for demanding distribution applications.
It excels in industrial power distribution, motor control centers, and process lines requiring precise protection coordination (P3) and high fault withstand. Its compact 186x205x103 mm footprint supports panel space optimization, while its robust mechanical durability is ideal for high-switching environments.
It carries IEC standard compliance and material declarations including RoHS, REACH, CMRT, and TSCA, along with WEEE packaging information. These declarations support global deployments and responsible supply chain management.
With a 15,000-cycle mechanical durability and 24.10 W power loss, it delivers reliable long-term protection with reduced maintenance and energy waste. The front-terminal design also shortens installation time and simplifies diagnostics during routine servicing.