ABB 1SDA116401R1 Moulded Case Circuit Breaker - SACE DSP

Part Number: 1SDA116401R1
Manufacturer
ABB
Part number
1SDA116401R1

Quick Summary

ABB 1SDA116401R1 Moulded Case Circuit Breaker protects power distribution panels in industrial automation, delivering reliable fault isolation up to 800 A. Engineers transitioning to higher line currents or compact switchboards struggle with coordinating protective settings and maintaining uptime during commissioning. This MCCB aligns with IEC safety standards and carries RoHS and REACH declarations, CMRT reporting, and TSCA compliance, supporting global supply chains. With a front-terminal design, a setting range of 560–800 A, and a 3-pole configuration, it offers scalable protection for P4-based power distribution while simplifying installation.

Product Information

Extended Description

1SDA116401R1 ABB: P4S 800 TMA 800-8000 3p F F
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221085090
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
9.5 kg
Package Level 1 Units
1 piece
Package Level 1 Width
305 mm
Package Level 1 Height
285 mm
Package Level 1 Depth / Length
370 mm
Package Level 1 Gross Weight
9.6 kg
Package Level 1 EAN
8056221085090
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P4
Version
F
Current Type
AC/DC
Mechanical Durability
15000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
54.20 W
Rated Current (In)
800 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
4000…8000 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 45 kA | (500 V AC) 16 kA | (250 V DC) 2 Poles in Series 35 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 45 kA | (500 V AC) 22 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
800 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMA
Release Type
TM
Setting Range
560…800 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P4
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
1SDH002127A1001
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Rated current of 800 A and adjustable setting range 560–800 A. Business Impact: Enables precise protection coordination for heavy feeders, reducing nuisance trips and enabling reliable panel operation. Application: Main feeders in manufacturing plants and distribution panels. Feature: Front-terminal connection and 3P arrangement. Business Impact: Simplifies wiring, speeds up installation, and improves serviceability in crowded switchgear enclosures. Application: New builds and retrofit projects with space constraints. Feature: Ics and Icu specifications (Ics up to 80 kA at 240 V AC; Icu up to 50 kA at 380–415 V AC; 22–35 kA at higher DC/AC variants). Business Impact: Enhanced fault endurance and selective tripping, minimizing downtime and collateral damage. Application: High-energy industrial networks requiring robust protection. Feature: RoHS/REACH/CMRT/TSCA compliance. Business Impact: Regulatory readiness across global sites and smoother supplier audits. Application: Global manufacturing and logistics environments with strict sustainability targets. Feature: Power loss and energy efficiency (54.20 W) with 15000 mechanical cycles. Business Impact: Lower operating costs and longer service life for critical protection devices. Application: Continuous operation in continuous process industries. Feature: Standards and compatibility (IEC, front-terminal, P4 suitability). Business Impact: Predictable performance and easy integration with SACE FORMULA DSP family. Application: Power distribution boards and control panels requiring dependable MCCB protection.

Get a Quick Quote for a ABB 1SDA116401R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours