ABB 1SDA116403R1 Moulded Case Circuit Breaker - 8 kV

Part Number: 1SDA116403R1
Manufacturer
ABB
Part number
1SDA116403R1

Quick Summary

ABB 1SDA116403R1 Moulded Case Circuit Breaker is designed to protect power distribution panels in industrial settings with high reliability and precise tripping. This 4-pole MCCB supports 800 A and operations at 500 V AC / 250 V DC, ideal for demanding control architectures. It helps reduce nuisance trips and maintenance by delivering predictable coordination in complex wiring. The device complies with IEC standards and carries RoHS and REACH declarations, along with TSCA information, offering regulatory assurance for global installations. For panel builders and machine OEMs, this MCCB delivers robust protection, streamlined integration with SACE FORMULA DSP, and scalable safety architecture for growing automation needs.

Product Information

Extended Description

1SDA116403R1 ABB: P4S 800 TMA 800-8000 4p F F InN=100%In
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221085113
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
12 kg
Package Level 1 Units
1 piece
Package Level 1 Width
305 mm
Package Level 1 Height
285 mm
Package Level 1 Depth / Length
370 mm
Package Level 1 Gross Weight
14 kg
Package Level 1 EAN
8056221085113
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P4
Version
F
Current Type
AC/DC
Mechanical Durability
15000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
54.20 W
Rated Current (In)
800 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
4000…8000 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC | 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 45 kA | (500 V AC) 16 kA | (250 V DC) 2 Poles in Series 35 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 45 kA | (500 V AC) 22 kA | (250 V DC) 2 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
800 A
Rated Voltage (Ur)
500 V AC | 250 V DC
Release
TMA
Release Type
TM
Setting Range
560…800 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P4
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
1SDH002127A1001
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 4P moulded case design provides compact yet rugged protection for high-current distribution, reducing cabinet footprint while improving fault containment in industrial control panels. This directly translates to lower installation time and material costs, and easier serviceability in retrofit projects. Feature → Business Impact → Application: Rated 800 A with a setting range of 560–800 A enables precise protection coordination and selective tripping, minimizing downtime during faults and ensuring continuity of critical loads in manufacturing lines and data centers. Feature → Business Impact → Application: Ii settings from 4000 to 8000 A and Ics up to 80 kA at 240 V / 50 kA at higher voltages deliver reliable short-circuit performance, reducing arc-flash risk and equipment damage in heavy machinery and conveyor systems. Feature → Business Impact → Application: Front-terminal connection simplifies installation and future upgrades, accelerating panel assembly and reducing field wiring errors in new builds and expansions. Feature → Business Impact → Application: RoHS, REACH, and TSCA declarations alongside IEC standards ensure regulatory compliance across regions, enabling global deployments for multinational projects. Feature → Business Impact → Application: Measured power loss of 54.20 W supports energy-aware design, contributing to lower operating costs in large-scale distribution centers and manufacturing floors. Feature → Business Impact → Application: Widespread compatibility with SACE FORMULA DSP systems enables seamless integration with existing protection schemes, improving overall safety architecture and lifecycle management for automation projects.

Get a Quick Quote for a ABB 1SDA116403R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA116403R1? Enquire Now