ABB 1SDA116430R1 Moulded Case Circuit Breaker - 3P 125A
Part Number: 1SDA116430R1
Quick Summary
ABB 1SDA116430R1 moulded case circuit breaker protects 3-phase power circuits in industrial control panels. It is engineered for reliable motor protection and panel-mount versatility, reducing nuisance trips and simplifying wiring in demanding environments. This device aligns with IEC standards and carries RoHS and REACH declarations, along with TSCA coverage for broader market compliance. With a compact front-connection design and adjustable short-circuit settings, it supports scalable motor protection schemes while enabling predictable maintenance cycles and lower total cost of ownership for automation projects.
Product Information
Extended Description
1SDA116430R1 ABB: P2S 250 MA125 Im=750...1500 3p F F
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221085380
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.6 kg
Package Level 1 Units
1 piece
Package Level 1 Width
155 mm
Package Level 1 Height
190 mm
Package Level 1 Depth / Length
155 mm
Package Level 1 Gross Weight
1.7 kg
Package Level 1 EAN
8056221085380
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P2
Version
F
Current Type
AC
Mechanical Durability
20000 cycle | 240 cycles per hour
Number of Poles
3P
Rated Current (In)
125 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
750...1500 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 20 kA | (500 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 80 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 40 kA | (500 V AC) 6 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
500 V AC
Release
MA
Release Type
M
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
P2
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
Installation instructions P2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 125 A rated current supports robust overload protection for medium-sized motor circuits, leading to fewer unplanned outages in automation lines and improved line efficiency in manufacturing cells. Application: Suitable for P2 motor protection in ABB SACE FORMULA DSP assemblies, enabling reliable protection in machine controls and panel boards. Feature → Business Impact → Application: Adjustable instantaneous trip setting (I_i) from 750 to 1500 A reduces nuisance trips during transient faults, delivering higher line availability and safer startup in process lines. Application: Ideal for drive and pump packs where precise coordination with motor starters is critical. Feature → Business Impact → Application: Front terminal connection simplifies wiring and field retrofit, cutting installation time by hours and reducing assembly errors in electrical switchgear. Application: Beneficial for new builds and retrofit projects in automation plants. Feature → Business Impact → Application: IEC standards compliance plus RoHS/REACH/TSCA declarations ensure regulatory alignment across EU and US markets, minimizing compliance risk and enabling global procurement. Application: Suitable for global sourcing and cross-border assembly. Feature → Business Impact → Application: 3P design and S (Short-Circuit) performance rating provide predictable protection during fault events, supporting safety and downtime reduction in critical production lines. Application: Critical for conveyors, material-handling systems, and multi-motor drives in industrial automation. Feature → Business Impact → Application: Compact dimensions (105 mm W x 150 mm H x 70 mm D) and weight (1.6 kg) enable dense panel layouts and easier enclosures, improving cabinet space utilization and reducing install footprint. Application: Useful in control panels with limited space or retrofits in existing switchgear.