ABB 1SDA116433R1 Moulded Case Circuit Breaker - 50 kA @ 240V IEC
Part Number: 1SDA116433R1
Quick Summary
ABB 1SDA116433R1 MCCB provides reliable motor protection for industrial drives and panels. In fast-moving production environments, nuisance trips and wiring complexity can derail uptime; this unit's precise I_i settings and robust fault withstand help minimize unplanned outages. It complies with IEC standards, is RoHS compliant, and supports CMRT tracking for responsible sourcing. Built for integration with the SACE FORMULA DSP family, it's ready for front-terminal installation in compact control panels, delivering straightforward wiring and quick commissioning. With its 320 A rating and 500 V AC capability, it offers scalable protection for medium-size motors while reducing repair costs and maintenance cycles. This MCCB aligns with modern safety and environmental requirements, boosting overall equipment efficiency and reliability.
Product Information
Extended Description
1SDA116433R1 ABB: P3N 400 MA320 Im=2240…4160 3p F F
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration
Environmental Information
Breakers - Packaging disposal information
EAN
8056221085410
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103 mm
Product Net Weight
4.8 kg
Package Level 1 Units
1 piece
Package Level 1 Width
248 mm
Package Level 1 Height
240 mm
Package Level 1 Depth / Length
285 mm
Package Level 1 Gross Weight
4.8 kg
Package Level 1 EAN
8056221085410
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE FORMULA DSP
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
P3
Version
F
Current Type
AC
Mechanical Durability
15000 cycle | 240 cycles per hour
Number of Poles
3P
Rated Current (In)
320 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
2240...4160 A
Rated Insulation Voltage (Ui)
750 V
Rated Operational Voltage
500 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 36 kA | (500 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 36 kA | (500 V AC) 20 kA
Rated Uninterrupted Current (Iu)
400 A
Rated Voltage (Ur)
500 V AC
Release
MA
Release Type
M
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
P3
Terminal Connection Type
Front
Data Sheet, Technical Information
Catalogue (.PDF) [ZH] FORMULA DSP MCCB
Instructions and Manuals
1SDH002124A1001
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Three-pole design rated to 320 A at 500 V AC provides robust protection for medium-size motors used in conveyors and machine tools. This enables selective tripping and reduces nuisance outages in year-round operation. The instantaneous trip setting is adjustable from 2240 to 4160 A, allowing precise coordination with motor starters and soft starters to prevent unnecessary trips during startup while preserving safety. In addition, the unit delivers short-circuit protection with I_cs up to 50 kA at 240 V and I_cu up to 20 kA at 500 V, ensuring safe interruption across a range of distribution voltages and minimizing arc fault risks in panel boards. Mechanical durability of 15,000 operation cycles (at 240 cycles/hour) supports high-usage environments, reducing replacement intervals and maintenance costs. Front-terminal connection simplifies installation and wiring in tight control panels, accelerating commissioning and facilitating retrofits. Compatibility with the SACE FORMULA DSP family enables seamless integration into existing motor protection schemes (P3) while maintaining a compact footprint. Compliance highlights include REACH and RoHS declarations, CMRT for conflict minerals, and TSCA declarations, which help meet global procurement and regulatory requirements and improve supplier transparency. By combining robust electrical performance with practical installation advantages and strong environmental compliance, this MCCB helps engineering teams reduce lifecycle costs while enhancing plant reliability.
Get a Quick Quote for a ABB 1SDA116433R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA116433R1?
Enquire Now